Operation Avoiding Resonance (Jump Frequency Function)
•
This function allows the prohibition or „jumping“ of certain frequencies within the Inverter’s output fre-
quency range so that the motor can operate without resonant oscillations caused by some machine systems.
•
It is also used for deadband control.
Related Parameters
Param-
eter-
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
LCD DIsplay
d3-01
Jump frequency 1
Set the frequency center value at which to prohibit set-
tings.
Set to 0.0 to disable the jump frequency.
Make sure the settings are as follows: d3-01
≥
d3-02
≥
d3-
03.
Operation within the jump frequency range is prohibited.
Changes during acceleration and deceleration are made
gradually without performing jumps.
0.0 to
120.0
0.0 Hz
No
A
Jump Freq 1
d3-02
Jump frequency 2
0.0 Hz
No
A
Jump Freq 2
d3-03
Jump frequency 3
0.0 Hz
No
A
Jump Freq 3
d3-04
Jump frequency width
Set the jump frequency width in hertz.
The jump frequency range is as follows: (Jump frequency
±d3-04).
0.0 to
20.0
1.0 Hz
No
A
Jump Bandwith
Frequency reference
Terminal A1 input voltage