Transportation Precautions
iii
Transportation Precautions
Installation Precautions
Wiring Precautions
Caution
Do not hold by front cover or panel. Instead hold by the cooling fins (heat
sink) while transporting the product. Doing so may result in injury.
Caution
Do not pull on the cables. Doing so may result in damge to the product or mal-
function.
Caution
Use the eyebolts only for transport of the Inverter. Using them to transport the
Inverter and attached equipment may result in injury or malfunction.
WARNING
Provide an appropriate stopping device on the machine side to secure safety. (
A holding brake is not a stopping device for securing safety) Not doing so may
result in injury.
WARNING
Provide an external emergency stopping device that allows an instantaneous
stop of operation and power interruption. Not doing so may result in injury.
Caution
Be sure to install the product in the correct direction and provide specified
clearances between the Inverter and control panel or with other devices to
allow for proper cooling. Not doing so may result in fire or malfunction.
Caution
Do not allow foreign objects to enter inside the product. Doing so may result in
fire and malfunction.
Caution
Do not apply any strong imact. Doing so may result in damage to the product
or malfunction.
WARNING
Wiring must be performed only after turning OFF the power supply. Not
doing so may result in electrical shock.
WARNING
Wiring must be performed by authorized personnel. Not doing so may result in
electrical shock.
WARNING
Be sur to confirm operation only after wiring the emergency stop circuit. Not
doing so may result in injury.
Required
Always connect the ground terminals to a ground of 100 Ohm or less for 200-
V AC class or 10 Ohm or less for the 400-V class. Not connecting to a proper
ground may result in electrical shock or fire.