Digital Operation Display Functions and Levels
5
-
5
d1-01
Frequency
reference 1
Set the frequency reference in the unit
specified in o1-03 (frequency units for
reference setting and monitor, default:
Hz)
0 to
50.00
0.00
Hz
Yes
Q
280H
Reference 1
d1-02
Frequency
reference 2
Frequency reference when multi-step
speed command 1 is ON for a multi-
function input (unit: Set in o1-03).
0.00
Hz
Yes
Q
281H
Reference 2
d1-03
Frequency
reference 3
Frequency reference when multi-step
speed command 2 is ON for a multi-
function input (unit: Set in o1-03).
0.00
Hz
Yes
Q
282H
Reference 3
d1-04
Frequency
reference 4
Frequency reference when multi-step
speed command 1 and 2 are ON for a
multi-function input (unit: Set in o1-
03).
0.00
Hz
Yes
Q
283H
Reference 4
d1-17
Jog fre-
quency refer-
ence
Frequency reference when multi-func-
tion inputs „Jog Frequency Com-
mand“, „FJOG command“ or „RJOG
command“ is ON (unit: Set in o1-03).
6.00
Hz
Yes
Q
292H
Jog
Reference
E1-01
Input voltage
setting
Set the Inverter input voltage in units
of 1 volt. This set value will be the
basis for the protection functions.
155 to
255
*2
200 V
*2
No
Q
300H
Input Voltage
E1-03
V/F pattern
selection
0 to D: Select from 14 preset patterns.
F:
Custom user-set patterns
(Applicable for setting E1-04
to E1-10).
0 to D,
F
F
No
Q
302H
V/F Selection
E1-04
Max. output
frequency
(FMAX)
0.0 to
120.0
50.0
Hz
No
Q
303H
Max
Frequency
E1-05
Max.
voltage
(VMAX)
0.0 to
255.0
*2
200.0
V
*2
No
Q
304H
Max
Voltage
E1-06
Base
frequency
(FA)
0.0 to
120.0
50.0
Hz
No
Q
305H
Base
Frequency
E1-09
Min. output
frequency
(FMIN)
0.0 to
120.0
1.5 Hz
No
Q
308H
Min.
Frequency
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
RS-422A/
485 Reg-
ister
LCD Display
Frequency
(Hz)
FMAX
(E1-04)
FA
(E1-06)
(E 1 -0 9)
FMIN
(E1-10)
VMIN
(E1-13)
VBASE
(E1-05)
VMAX
Output voltage (V)