651
Auxiliary Area Allocations by Address
Appendix D
A302
A302.00
to
A302.15
CPU Bus Unit
Initializing
Flags
These flags are ON while the corre-
sponding CPU Bus Unit is initializing
after its CPU Bus Unit Restart Bit
(A501.00 to A501.15) is turned ON
or the power is turned ON.
Bits 00 to 15 correspond to unit num-
bers 0 to 15.
Use these flags in the program to
prevent the CPU Bus Unit’s refresh
data from being used while the Unit
is initializing. IORF(097) cannot be
executed while an CPU Bus Unit is
initializing.
These bits are turned OFF automati-
cally when initialization is completed.
OFF: Not ini-
tializing
ON: Initializ-
ing
(Reset to 0
automatically
after initializa-
tion.)
Retained
Cleared
Written
during ini-
tialization
A501.00
to
A501.15
A310
All
Manufactur-
ing Lot Num-
ber, Lower
Digits
The manufacturing lot number is
stored in 6 digits hexadecimal. X, Y,
and Z in the lot number are con-
verted to 10, 11, and 12, respec-
tively.
Examples:
Lot number 01805
A310 = 0801, A311 = 0005
Lot number 30Y05
A310 =1130, A311 = 0005
---
Retained
Retained ---
---
A311
All
Manufactur-
ing Lot Num-
ber, Upper
Digits
A315
A315.13 Option Board
Error Flag
ON when the Option Board is
removed while the power is being
supplied. CPU Unit operation will
continue and the ERR/ALM indicator
will flash.
OFF when the error has been
cleared.
---
Cleared
Cleared
Refreshed
when error
occurs.
A402.00,
A424
A315.14 Built-in Ana-
log I/O Error
Flag
ON when a built-in analog I/O error
occurs and stops the operation of
built-in analog I/O. CPU Unit opera-
tion will continue and the ERR/ALM
indicator will flash.
OFF when the error has been
cleared.
---
Cleared
Cleared
Refreshed
when error
occurs.
A402.00
A315.15 Flash Mem-
ory Error Flag
ON when writing to the internal flash
memory fails. CPU Unit operation will
continue and the ERR/ALM indicator
will flash.
OFF when the error has been
cleared.
---
Cleared
Cleared
Refreshed
when error
occurs.
A402.00
A316
to
A317
All
High-speed
Counter 2 PV
Contains the PV of high-speed
counter 2. A317 contains the left-
most 4 digits and A316 contains the
rightmost 4 digits.
The PV is cleared when operation
starts.
---
---
Cleared
Refreshed
each cycle
during
oversee
process.
Refreshed
when
PRV(881)
instruction
is exe-
cuted.
---
A318
to
A319
All
High-speed
Counter 3 PV
Contains the PV of high-speed
counter 3. A319 contains the left-
most 4 digits and A318 contains the
rightmost 4 digits.
The PV is cleared when operation
starts.
---
---
Cleared
---
A320
A320.00 High-speed
Counter 2
Range 1 Com-
parison Condi-
tion Met Flag
These flags indicate whether the PV
is within the specified ranges when
high-speed counter 2 is being oper-
ated in range-comparison mode.
Cleared at beginning of operation.
Cleared when range comparison
table is registered.
OFF: PV not in range
ON: PV in range
---
---
Cleared
Refreshed
each cycle
during
oversee
process.
Refreshed
when
PRV(881)
instruction
is exe-
cuted.
---
Address
Name
Function
Settings
Status
after
mode
change
Status
at star-
tup
Write
timing
Related
flags, set-
tings
Words
Bits
Содержание CP1H CPU UNITS - PROGRAMMING 05-2007
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Страница 370: ...336 Analog I O XA CPU Units Section 5 5...
Страница 552: ...518 Trouble Shooting Section 8 7...
Страница 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 598: ...564 Sample Application Section 9 12...
Страница 642: ...608 Standard Models Appendix A...
Страница 643: ...609 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 652: ...618 Dimensions Diagrams Appendix B...
Страница 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Страница 776: ...742 PLC Setup Appendix G...
Страница 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Страница 786: ...752 Revision History...