57
Specifications
Section 2-2
Interrupt Inputs and
Quick-response Inputs
Input bits CIO 0.00 to CIO 0.03 and CIO 1.00 to CIO 1.03 can be used not
only as normal inputs but also as interrupt or quick-response inputs depend-
ing on the settings in the PLC Setup.
The ON/OFF response time is 8 ms for normal inputs, but it can be changed
in the PLC Setup to 0, 0.5, 1, 2, 4, 8, 16, or 32 ms.
Relationship between Built-in Outputs and Terminal Block Arrangement
Terminal Block Arrangement
Setting Functions Using
Instructions and PLC
Setup
Pulses can be output from the normal output terminals in the built-in outputs
by executing pulse output instructions. To use the ORIGIN SEARCH (ORG)
instruction, all of the pulse output settings in the PLC Setup must be set.
Input bit
Interrupt inputs
Quick-response inputs
CIO 0.00
Interrupt input 0
Quick-response input 0
CIO 0.01
Interrupt input 1
Quick-response input 1
CIO 0.02
Interrupt input 2
Quick-response input 2
CIO 0.03
Interrupt input 3
Quick-response input 3
CIO 1.00
Interrupt input 4
Quick-response input 4
CIO 1.01
Interrupt input 5
Quick-response input 5
CIO 1.02
Interrupt input 6
Quick-response input 6
CIO 1.03
Interrupt input 7
Quick-response input 7
NC
00
01
02
03
04
06
00
01
03
04
06
NC
COM
COM
COM COM
05
07
COM
02
COM
05
07
Lower Terminal Block (Example: Transistor Outputs)
CIO 100
CIO 101
Normal output terminals
Output
terminal
block
When the
instructions to
the right are
not executed
When a pulse output instruction
(SPED, ACC, PLS2, or ORG) is
executed
When the origin search
function is set to be used in
the PLC Setup, and an
origin search is executed by
the ORG instruction
When the PWM
instruction is
executed
Word
Bit
Normal
outputs
Fixed duty ratio pulse output
Variable duty ratio
pulse output
CW/CCW
Pulse plus
direction
+ When the origin search
function is used
PWM output
CIO
100
00
Normal output 0 Pulse output 0
(CW)
Pulse output 0
(pulse)
---
---
01
Normal output 1 Pulse output 0
(CCW)
Pulse output 1
(pulse)
---
---
02
Normal output 2 Pulse output 1
(CW)
Pulse output 0
(direction)
---
---
03
Normal output 3 Pulse output 1
(CCW)
Pulse output 1
(direction)
---
---
04
Normal output 4 Pulse output 2
(CW)
Pulse output 2
(pulse)
---
---
05
Normal output 5 Pulse output 2
(CCW)
Pulse output 2
(direction)
---
---
06
Normal output 6 Pulse output 3
(CW)
Pulse output 3
(pulse)
---
---
07
Normal output 7 Pulse output 3
(CCW)
Pulse output 3
(direction)
---
---
Содержание CP1H CPU UNITS - PROGRAMMING 05-2007
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Страница 370: ...336 Analog I O XA CPU Units Section 5 5...
Страница 552: ...518 Trouble Shooting Section 8 7...
Страница 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 598: ...564 Sample Application Section 9 12...
Страница 642: ...608 Standard Models Appendix A...
Страница 643: ...609 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 652: ...618 Dimensions Diagrams Appendix B...
Страница 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Страница 776: ...742 PLC Setup Appendix G...
Страница 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Страница 786: ...752 Revision History...