674
Auxiliary Area Allocations by Address
Appendix D
Note
These Auxiliary Area bits/words are not to be written by the user. The number of resends and response
monitoring time must be set by the user in the FB communications instructions settings in the PLC
Setup, particularly when using function blocks from the OMRON FB Library to execute FINS messages
or DeviceNet explicit messages communications. The values set in the Settings for OMRON FB Library
in the PLC Setup will be automatically stored in the related Auxiliary Area words A580 to A582 and used
by the function blocks from the OMRON FB Library.
A543
A543.10 Pulse Out-
put 3 Posi-
tioning
Completed
Signal
This is the positioning completed
input signal used in the origin search
for pulse output 3. The input signal
from the servo driver is output to this
bit from the ladder program to enable
using the signal.
---
---
---
---
---
A544
All
Interrupt
Counter 4
Counter SV
Used for an input interrupt in Counter
Mode. Set the value to count before
starting the interrupt task. When
interrupt counter 4 has counted the
set number of pulses, interrupt task
144 will be started.
---
---
Retained
---
---
A545
All
Interrupt
Counter 5
Counter SV
Used for an input interrupt in Counter
Mode. Set the value to count before
starting the interrupt task. When
interrupt counter 5 has counted the
set number of pulses, interrupt task
145 will be started.
---
---
Retained
---
---
A546
All
Interrupt
Counter 7
Counter SV
Used for an input interrupt in Counter
Mode. Set the value to count before
starting the interrupt task. When
interrupt counter 6 has counted the
set number of pulses, interrupt task
146 will be started.
---
---
Retained
---
---
A547
All
Interrupt
Counter 7
Counter SV
Used for an input interrupt in Counter
Mode. Set the value to count before
starting the interrupt task. When
interrupt counter 7 has counted the
set number of pulses, interrupt task
147 will be started.
---
---
Retained
---
---
A548
All
Interrupt
Counter 4
Counter PV
Stores the present value of the inter-
rupt counter for an input interrupt in
Counter Mode.
For an incrementing counter, the
value is incremented by 1 from 0.
The value returns to 0 after the SV
has been reached.
For a decrementing counter, the
value is decremented by 1 from the
ST. The value returns to the SV after
0 has been reached.
---
---
Cleared
Cleared
---
A549
All
Interrupt
Counter 5
Counter PV
---
---
Cleared
Cleared
---
A550
All
Interrupt
Counter 7
Counter PV
---
---
Cleared
Cleared
---
A551
All
Interrupt
Counter 7
Counter PV
---
---
Cleared
Cleared
---
A580
(See
note.)
A580.00
to
A580.03
FB Commu-
nications
Instruction
Retries
Automatically stores the number of
retries in the FB communications
instruction settings specified in the
PLC Setup.
0 to F hex
---
Cleared
Written at
start of
operation
A581
(See
note.)
All
FB Commu-
nications
Instruction
Response
Monitoring
Time
Automatically stores the FB commu-
nications instruction response moni-
toring time set in the PLC Setup.
0001 to FFFF
hex (Unit: 0.1 s;
Range: 0.1 to
6553.5)
0000 hex: 2 s
---
Cleared
Written at
start of
operation
---
A582
(See
note.)
All
FB
DeviceNet
Communica-
tions
Instruction
Response
Monitoring
Time
Automatically stores the FB
DeviceNet communications instruc-
tion response monitoring time set in
the PLC Setup.
0001 to FFFF
hex (Unit: 0.1 s;
Range: 0.1 to
6553.5)
0000 hex: 2 s
---
Cleared
Written at
start of
operation
---
Addresses
Name
Function
Settings
Status
after
mode
change
Status at
startup
Write
timing
Related
Flags,
Settings
Word
Bits
Содержание CP1H CPU UNITS - PROGRAMMING 05-2007
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Страница 370: ...336 Analog I O XA CPU Units Section 5 5...
Страница 552: ...518 Trouble Shooting Section 8 7...
Страница 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 598: ...564 Sample Application Section 9 12...
Страница 642: ...608 Standard Models Appendix A...
Страница 643: ...609 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 652: ...618 Dimensions Diagrams Appendix B...
Страница 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...