661
Auxiliary Area Allocations by Address
Appendix D
A401
A401.09 Program Error
Flag
(fatal error)
ON when program contents are
incorrect.
CPU Unit operation will stop and the
ERR/ALM indicator on the front of
the CPU Unit will light. The task num-
ber where the error occurred will be
stored in A294 and the program
address will be stored in A298 and
A299.
The type of program error that
occurred will be stored in A295.08 to
A295.15. Refer to the description of
A295 for more details on program
errors.
This flag will be turned OFF when
the error is cleared.
ON: Error
OFF: No error
Cleared
Cleared
Refreshed
when error
occurs.
A294,
A295,
A298 and
A299
A401.10 I/O Setting
Error Flag
(fatal error)
ON when a Basic I/O Unit or I/O
Control Unit is mounted. (These
Units cannot be used.)
CPU Unit operation will stop and the
ERR/ALM indicator on the front of
the CPU Unit will light.
This flag will be turned OFF when
the error is cleared.
ON: Error
OFF: No error
Cleared
Cleared
Refreshed
when error
occurs.
A405.08
A401.11 Too Many I/O
Points Flag
(fatal error)
ON when the number of CP-series
Expansion Units and Expansion I/O
Units exceeds the limit, when the
number of words allocated to these
Units exceeds the limit, or when too
many CJ-series Units are mounted.
CPU Unit operation will stop and the
ERR/ALM indicator on the front of
the CPU Unit will light.
This flag will be turned OFF when
the error is cleared.
ON: Error
OFF: No error
Cleared
Cleared
Refreshed
when error
occurs.
A407
A401.13 Duplication
Error Flag
(fatal error)
ON in the following cases:
• Two CPU Bus Units have been
assigned the same unit number.
• Two Special I/O Units have been
assigned the same unit number.
CPU Unit operation will stop and the
ERR/ALM indicator on the front of
the CPU Unit will light.
The duplicated unit number is indi-
cated in A409 to A416.
(This flag will be turned OFF when
the error is cleared.)
ON: Duplica-
tion error
OFF: No
duplication
Cleared
Cleared
Refreshed
when error
occurs.
A410 to
A416
Address
Name
Function
Settings
Status
after
mode
change
Status
at star-
tup
Write
timing
Related
flags, set-
tings
Words
Bits
Содержание CP1H CPU UNITS - PROGRAMMING 05-2007
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Страница 370: ...336 Analog I O XA CPU Units Section 5 5...
Страница 552: ...518 Trouble Shooting Section 8 7...
Страница 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 598: ...564 Sample Application Section 9 12...
Страница 642: ...608 Standard Models Appendix A...
Страница 643: ...609 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 652: ...618 Dimensions Diagrams Appendix B...
Страница 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Страница 776: ...742 PLC Setup Appendix G...
Страница 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Страница 786: ...752 Revision History...