118
Wiring CP1H CPU Units
Section 3-4
• If one phase of the power supply is grounded, connect the grounded
phase to the L2/N terminal.
• The GR terminal is a ground terminal. To prevent electrical shock, use a
dedicated ground line (2 mm
2
min.) of 100
Ω
or less.
• The line ground terminal (LG) is a noise-filtered neutral terminal. If noise
is a significant source of errors or if electrical shocks are a problem, con-
nect the line ground terminal (LG) to the ground terminal (GR) and ground
both with a ground resistance of 100
Ω
or less.
• To prevent electrical shock when short-circuiting between the LG and GR
terminals, always use a ground of 100
Ω
or less.
• Do not connect ground lines to other devices or to the frame of a building.
Doing so will reverse the effectiveness of the ground and instead have a
bad influence.
Isolating Transformer
The PLC's internal noise control is sufficient for the general noise to which
power supply lines are subjected. Ground noise can be further reduced by
providing the power supply through a 1:1 isolating transformer. Leave the iso-
lating transformer's secondary side ungrounded.
CPU Units with DC Power Supply
DC Power Supply Wiring
• Use crimp terminals or solid wire for wiring the power supply. Do not con-
nect bare stranded wires directly to terminals.
• M3 self-rising terminal screws are used. Tighten the terminal screws to
the torque of 0.5 N·m.
• To prevent noise, use a ground of 100
Ω
or less.
DC Power Supply
• Provide a power supply of 20.4 to 26.4 VDC unless there are two or more
Expansion Units and Expansion I/O Units. Provide a power supply of 21.6
to 26.4 VDC if there are two or more Expansion Units and Expansion I/O
Units.
• The maximum current consumption is 50 W per device.
• When the power supply is turned ON, the inrush current is approximately
five times the normal current.
• The GR terminal is a ground terminal. To prevent electrical shock, use a
dedicated ground line (2 mm
2
min.) of 100
Ω
or less.
+
−
COM
01
03
05
07
09
11
01
03
05 07
09 11
NC
00 02
04
06
08
10
00
02
04
06
08
10
−
+
24 VDC
Circuit protector
Upper terminal block
Ground (100
Ω
or less)
GR: Protective ground terminal
6.2 mm max.
6.2 mm max.
Содержание CP1H CPU UNITS - PROGRAMMING 05-2007
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Страница 370: ...336 Analog I O XA CPU Units Section 5 5...
Страница 552: ...518 Trouble Shooting Section 8 7...
Страница 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 598: ...564 Sample Application Section 9 12...
Страница 642: ...608 Standard Models Appendix A...
Страница 643: ...609 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 652: ...618 Dimensions Diagrams Appendix B...
Страница 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Страница 776: ...742 PLC Setup Appendix G...
Страница 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Страница 786: ...752 Revision History...