148
Overview of I/O Memory Area
Section 4-1
4-1-3
Clearing and Holding I/O Memory
Note
1.
Mode changed from PROGRAM to RUN/MONITOR or vice-versa.
2.
The PLC Setup’s
IOM Hold Bit Status at Startup
setting determines wheth-
er the IOM Hold Bit’s status is held or cleared when the PLC is turned ON.
4-1-4
Hot Start/Hot Stop Functions
Operating Mode Changes
Hot Start
Turn ON the IOM Hold Bit to retain all data* in I/O memory when the CPU Unit
is switched from PROGRAM mode to RUN/MONITOR mode to start program
execution.
Hot Stop
When the IOM Hold Bit is ON, all data* in I/O memory will also be retained
when the CPU Unit is switched from RUN or MONITOR mode to PROGRAM
mode to stop program execution.
Area
Mode changed
1
Fatal error generated
PLC power turned ON
Execution of FALS
Other fatal errors
PLC Setup set to
clear IOM Hold Bit
status
2
PLC Setup set to
hold IOM Hold Bit
status
2
IOM Hold
Bit OFF
IOM Hold
Bit ON
IOM Hold
Bit OFF
IOM Hold
Bit ON
IOM Hold
Bit OFF
IOM Hold
Bit ON
IOM Hold
Bit OFF
IOM Hold
Bit ON
IOM Hold
Bit OFF
IOM Hold
Bit ON
CIO
Area
I/O Area
Cleared
Retained
Retained
Retained
Cleared
Retained
Cleared
Cleared
Cleared
Retained
Built-in Analog I/O Areas
(XA CPU Units only)
Data Link Area
CPU Bus Unit Area
Special I/O Unit Area
Serial PC Link Area
DeviceNet Area
Internal I/O Area
Work Area (W)
Cleared
Retained
Retained
Retained
Cleared
Retained
Cleared
Cleared
Cleared
Retained
Holding Area (H)
Retained
Retained
Retained
Retained
Retained
Retained
Retained
Retained
Retained
Retained
Auxiliary Area (A)
Status treatment depends on address.
Data Memory Area (D)
Retained
Retained
Retained
Retained
Retained
Retained
Retained
Retained
Retained
Retained
Timer Completion Flags (T)
Cleared
Retained
Retained
Retained
Cleared
Retained
Cleared
Cleared
Cleared
Retained
Timer PVs (T)
Cleared
Retained
Retained
Retained
Cleared
Retained
Cleared
Cleared
Cleared
Retained
Counter Completion Flags (C)
Retained
Retained
Retained
Retained
Retained
Retained
Retained
Retained
Retained
Retained
Counter PVs (C)
Retained
Retained
Retained
Retained
Retained
Retained
Retained
Retained
Retained
Retained
Task Flags (TK)
Cleared
Cleared
Retained
Retained
Cleared
Cleared
Cleared
Cleared
Cleared
Cleared
Index Registers (IR)
Cleared
Retained
Retained
Retained
Cleared
Retained
Cleared
Cleared
Cleared
Retained
Data Registers (DR)
Cleared
Retained
Retained
Retained
Cleared
Retained
Cleared
Cleared
Cleared
Retained
PROGRAM
Retain
I/O memory
CIO and
other areas
MONITOR or RUN
PROGRAM
Retain
MONITOR or RUN
I/O memory
CIO and
other areas
Содержание CP1H CPU UNITS - PROGRAMMING 05-2007
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Страница 370: ...336 Analog I O XA CPU Units Section 5 5...
Страница 552: ...518 Trouble Shooting Section 8 7...
Страница 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 598: ...564 Sample Application Section 9 12...
Страница 642: ...608 Standard Models Appendix A...
Страница 643: ...609 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 652: ...618 Dimensions Diagrams Appendix B...
Страница 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Страница 776: ...742 PLC Setup Appendix G...
Страница 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Страница 786: ...752 Revision History...