202
Interrupt Functions
Section 5-1
Y CPU Units
Input Terminal Arrangement
Input Function Settings in the PLC Setup
The CPU Unit’s built-in inputs can be set for high-speed counter inputs in the
PLC Setup’s Built-in Input Tab. (When an input is set for use as a high-speed
counter input, the corresponding words and bits cannot be used for general-
purpose (normal) inputs, input interrupts, or quick-response inputs.)
High-speed counter 0
(Phase B, Decrement, or
Direction input)
High-speed counter 0
(Phase Z or Reset input)
High-speed counter 0
(Phase A, Increment, or
Count input)
High-speed counter 1
(Phase B, Decrement, or
Direction input)
High-speed counter 1
(Phase Z or Reset input)
High-speed counter 1
(Phase A, Increment, or
Count input)
High-speed counter 2
(Phase B, Decrement, or
Direction input)
High-speed counter 3
(Phase B, Decrement, or
Direction input)
High-speed counter 2
(Phase Z or Reset input)
Upper Terminal Block
Inputs
(CIO 0)
Inputs (CIO 1)
High-speed counter terminals
00
04
10
00
02
04
−
COM
01
05
11
01
03
05
NC
A0
+
B0
+
Z0
+
A1
+
B1
+
Z1
+
A0
−
B0
−
Z0
−
A1
−
B1
−
Z1
−
+
High-speed counter 3
(Phase Z or Reset input)
High-speed counter 3
(Phase A, Increment, or
Count input)
High-speed counter 2
(Phase A, Increment, or
Count input)
Input terminal
block
Bit function when the high-speed counter is enabled by
selecting “Use high-speed counter
@
” in the PLC Setup
Word
Bit
---
A0
High-speed counter 0 (Phase A, Increment, or Count input)
---
B0
High-speed counter 0 (Phase B, Decrement, or Direction input)
---
Z0
High-speed counter 0 (Phase Z or reset input)
---
A1
High-speed counter 1 (Phase A, Increment, or Count input)
---
B1
High-speed counter 1 (Phase B, Decrement, or Direction input)
---
Z1
High-speed counter 1 (Phase Z or reset input)
CIO 0
00
---
01
High-speed counter 2 (Phase A, Increment, or Count input)
04
High-speed counter 2 (Phase B, Decrement, or Direction input)
05
High-speed counter 2 (Phase Z or reset input)
10
High-speed counter 3 (Phase A, Increment, or Count input)
11
High-speed counter 3 (Phase B, Decrement, or Direction input)
CIO 1
00
High-speed counter 3 (Phase Z or reset input)
01 to 05
---
Содержание CP1H CPU UNITS - PROGRAMMING 05-2007
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Страница 370: ...336 Analog I O XA CPU Units Section 5 5...
Страница 552: ...518 Trouble Shooting Section 8 7...
Страница 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 598: ...564 Sample Application Section 9 12...
Страница 642: ...608 Standard Models Appendix A...
Страница 643: ...609 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 652: ...618 Dimensions Diagrams Appendix B...
Страница 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Страница 776: ...742 PLC Setup Appendix G...
Страница 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Страница 786: ...752 Revision History...