166
Timers and Counters
Section 4-13
The refresh method for timer PVs can be set from the CX-Programmer to
either BCD or binary.
Note
It is not recommended to use the same timer number in two timer instructions
because the timers will not operate correctly if they are timing simultaneously.
(If two or more timer instructions use the same timer number, an error will be
generated during the program check, but the timers will operate as long as the
instructions are not executed in the same cycle.)
The following table shows when timers will be reset or maintained.
Note
1.
If the IOM Hold Bit (A500.12) is ON, the PV and Completion Flag will be
retained when a fatal error occurs (including execution of FALS instruc-
tions) or the operating mode is changed from PROGRAM mode to RUN or
MONITOR mode or vice-versa. The PV and Completion Flag will be
cleared when power is cycled.
2.
If the IOM Hold Bit (A50012) is ON and the PLC Setup’s
IOM Hold Bit Sta-
tus at Startup
setting is set to protect the IOM Hold Bit, the PV and Com-
pletion Flag will be retained when the PLC’s power is cycled.
3.
Since the TIML(542), TIMLX(553), MTIM(543), and MTIMX(554) instruc-
tions do not use timer numbers, they are reset under different conditions.
Refer to the descriptions of these instructions for details.
4.
The present value of TIM, TIMX(550), TIMH(015), TIMHX(551), TM-
HH(540), TMHHX(552), TIMW(813), TIMWX(816), TMHW(815) and TMH-
WX(817) timers programmed with timer numbers 0000 to 2047 will be
updated even when jumped between JMP and JME instructions or when
in a task that is on standby. The present value of timers programmed with
timer numbers 2048 to 4095 will be held when jumped or when in a task
that is on standby.
Forcing Bit Status
Timer Completion Flags can be force-set and force-reset.
Timer PVs cannot be force-set or force-reset, although the PVs can be
refreshed indirectly by force-setting/resetting the Completion Flag.
Restrictions
There are no restrictions in the order of using timer numbers or in the number
of N.C. or N.O. conditions that can be programmed. Timer PVs can be read as
word data and used in programming.
Instruction name
Effect on PV and Completion Flag
Operation in
Jumps and Interlocks
Mode change
1
PLC start-up
2
CNR(545)/CN
RX(547)
Jumps
(JMP-JME) or
Tasks on
standby
4
Interlocks
(IL-ILC)
TIMER: TIM/TIMX(550)
PV
→
0
Flag
→
OFF
PV
→
0
Flag
→
OFF
PV
→
9999
Flag
→
OFF
PVs refreshed in
operating timers
PV
→
SV
(Reset to SV.)
Flag
→
OFF
HIGH-SPEED TIMER:
TIMH(015)/TIMHX(551)
ONE-MS TIMER:
TMHH(540)/TMHHX(552)
ACCUMULATIVE TIMER:
TTIM(087)/TTIMX(555)
PV Maintained
PV Maintained
TIMER WAIT:
TIMW(813)TIMWX(816)
PVs refreshed in
operating timers
---
HIGH-SPEED TIMER WAIT:
TMHW(815)/TMHWX(817)
---
Содержание CP1H CPU UNITS - PROGRAMMING 05-2007
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Страница 370: ...336 Analog I O XA CPU Units Section 5 5...
Страница 552: ...518 Trouble Shooting Section 8 7...
Страница 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 598: ...564 Sample Application Section 9 12...
Страница 642: ...608 Standard Models Appendix A...
Страница 643: ...609 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 652: ...618 Dimensions Diagrams Appendix B...
Страница 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Страница 776: ...742 PLC Setup Appendix G...
Страница 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Страница 786: ...752 Revision History...