230
Pulse Outputs
Section 5-3
5-3-2
Pulse Output Specifications
Specifications
Change speed in steps
(polyline approxima-
tion) during speed con-
trol.
Use the ACC(888) instruction (con-
tinuous) to change the acceleration
rate or deceleration rate.
When a speed control operation started with the
ACC(888) instruction (continuous) is in progress,
another ACC(888) instruction (continuous) can be exe-
cuted to change the acceleration rate or deceleration
rate.
Change speed in steps
(polyline approxima-
tion) during positioning.
Use the ACC(888) instruction (inde-
pendent) or PLS2(887) to change the
acceleration rate or deceleration rate.
When a positioning operation started with the ACC(888)
instruction (independent) or PLS2(887) instruction is in
progress, another ACC(888) (independent) or
PLS2(887) instruction can be executed to change the
acceleration rate or deceleration rate.
Perform fixed distance
feed interrupt.
Execute positioning with the
PLS2(887) instruction during an
operation started with SPED(885)
(continuous) or ACC(888) (continu-
ous).
When a speed control operation started with the
SPED(885) instruction (continuous) or ACC(888)
instruction (continuous) is in progress, the PLS2(887)
instruction can be executed to switch to positioning, out-
put a fixed number of pulses, and stop.
After determining the
origin, perform position-
ing simply in absolute
coordinates without
regard to the direction
of the current position
or target position.
The positioning direction is selected
automatically in the absolute coordi-
nate system.
When operating in absolute coordinates (with the origin
determined or INI(880) instruction executed to change
the PV), the CW or CCW direction is selected automati-
cally based on the relationship between the pulse output
PV and the pulse Output Amount specified when the
pulse output instruction is executed.
Perform triangular con-
trol.
Positioning with the ACC(888)
instruction (independent) or
PLS2(887) instruction.
When a positioning operation started with the ACC(888)
instruction (independent) or PLS2(887) instruction is in
progress, triangular control (trapezoidal control without
the constant-speed plateau) will be performed if the
number of output pulses required for acceleration/decel-
eration exceeds the specified target pulse Output
Amount.
(The number of pulses required for acceleration/deceler-
ation equals the time required to reach the target fre-
quency x the target frequency.)
Use variable duty factor
outputs for time-propor-
tional temperature con-
trol.
Control with analog inputs and the
variable duty factor pulse output func-
tion (PWM(891)).
Two built-in outputs can be used as PWM(891) outputs 0
and 1 by executing the PWM(891) instruction.
Item
Specifications
Output mode
Continuous mode (for speed control) or independent mode (for position control)
Positioning (independent mode)
instructions
PULS(886) and SPED(885), PULS(886) and ACC(888), or PLS2(887)
Speed control (continuous mode)
instructions
SPED(885) or ACC(888)
Origin (origin search and origin
return) instructions
ORG(889)
Output frequency
X/XA CPU Units:
Unit version 1.1 and later:
Pulse outputs 0, 1, 2, 3: 1 Hz to 100 kHz (1 Hz units)
Unit version 1.0 and earlier:
Pulse outputs 0 and 1: 1 Hz to 100 kHz (1 Hz units)
Pulse outputs 2 and 3: 1 Hz to 30 kHz (1 Hz units)
Y CPU Units:
Pulse outputs 0 and 1: 1 Hz to 1 MHz (1 Hz units)
Pulse outputs 2 and 3: 1 Hz to 100 kHz (1 Hz units)
Purpose
Function
Description
Содержание CP1H CPU UNITS - PROGRAMMING 05-2007
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Страница 370: ...336 Analog I O XA CPU Units Section 5 5...
Страница 552: ...518 Trouble Shooting Section 8 7...
Страница 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 598: ...564 Sample Application Section 9 12...
Страница 642: ...608 Standard Models Appendix A...
Страница 643: ...609 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 652: ...618 Dimensions Diagrams Appendix B...
Страница 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Страница 776: ...742 PLC Setup Appendix G...
Страница 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Страница 786: ...752 Revision History...