672
Auxiliary Area Allocations by Address
Appendix D
A531
A531.08 High-speed
Counter 0
Gate Bit
When a counter's Gate Bit is ON, the
counter's PV will not be changed
even if pulse inputs are received for
the counter.
When the bit is turned OFF again,
counting will restart and the high-
speed counter's PV will be refreshed.
When the reset method is set to
Phase-Z Software reset, the
Gate Bit is disabled while the corre-
sponding Reset Bit (A531.00 or
A531.01) is ON.
---
Retained
Cleared
---
---
A531.09 High-speed
Counter 1
Gate Bit
---
Retained
Cleared
---
---
A531.10 High-speed
Counter 2
Gate Bit
---
Retained
Cleared
---
---
A531.11 High-speed
Counter 3
Gate Bit
---
Retained
Cleared
---
---
A532
All
Interrupt
Counter 0
Counter SV
Used for interrupt input 0 in counter
mode.
Sets the count value at which the
interrupt task will start. Interrupt task
140 will start when interrupt counter
0 has counted this number of pulses.
Retained when operation starts.
---
Retained
Retained
---
---
A533
All
Interrupt
Counter 1
Counter SV
Used for interrupt input 1 in counter
mode.
Sets the count value at which the
interrupt task will start. Interrupt task
141 will start when interrupt counter
1 has counted this number of pulses.
---
Retained
Retained
---
---
A534
All
Interrupt
Counter 2
Counter SV
Used for interrupt input 2 in counter
mode.
Sets the count value at which the
interrupt task will start. Interrupt task
142 will start when interrupt counter
2 has counted this number of pulses.
---
Retained
Retained
---
---
A535
All
Interrupt
Counter 3
Counter SV
Used for interrupt input 3 in counter
mode.
Sets the count value at which the
interrupt task will start. Interrupt task
143 will start when interrupt counter
3 has counted this number of pulses.
---
Retained
Retained
---
---
A536
All
Interrupt
Counter 0
Counter PV
These words contain the interrupt
counter PVs for interrupt inputs oper-
ating in counter mode.
In increment mode, the counter PV
starts incrementing from 0. When the
counter PV reaches the counter SV,
the PV is automatically reset to 0.
In decrement mode, the counter PV
starts decrementing from the counter
SV. When the counter PV reaches
the 0, the PV is automatically reset to
the SV.
Cleared when operation starts.
---
---
Retained
Refresh-
ed when
interrupt
is gener-
ated.
Refresh-
ed when
INI(880)
instruc-
tion is
executed.
---
A537
All
Interrupt
Counter 1
Counter PV
---
---
---
A538
All
Interrupt
Counter 2
Counter PV
---
---
---
A539
All
Interrupt
Counter 3
Counter PV
---
---
---
A540
A540.00 Pulse Out-
put 0 Reset
Bit
The pulse output 0 PV (contained in
A276 and A277) will be cleared when
this bit is turned ON.
---
---
Cleared
---
A276 and
A277
A540.08 Pulse Out-
put 0 CW
Limit Input
Signal Flag
This is the CW limit input signal for
pulse output 0, which is used in the
origin search. To use this signal,
write the input from the actual sensor
as an input condition in the ladder
program and output the result to this
flag.
---
---
Cleared
---
---
A540.09 Pulse Out-
put 0 CCW
Limit Input
Signal Flag
This is the CCW limit input signal for
pulse output 0, which is used in the
origin search. To use this signal,
write the input from the actual sensor
as an input condition in the ladder
program and output the result to this
flag.
---
---
Cleared
---
---
Addresses
Name
Function
Settings
Status
after
mode
change
Status at
startup
Write
timing
Related
Flags,
Settings
Word
Bits
Содержание CP1H CPU UNITS - PROGRAMMING 05-2007
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Страница 370: ...336 Analog I O XA CPU Units Section 5 5...
Страница 552: ...518 Trouble Shooting Section 8 7...
Страница 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 598: ...564 Sample Application Section 9 12...
Страница 642: ...608 Standard Models Appendix A...
Страница 643: ...609 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 652: ...618 Dimensions Diagrams Appendix B...
Страница 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Страница 776: ...742 PLC Setup Appendix G...
Страница 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Страница 786: ...752 Revision History...