637
Auxiliary Area Allocations by Function
Appendix C
Modbus-RTU Easy Master Information
Note
DM fixed allocation words for Modbus-RTU Easy Master for serial port 1: D32200 to D32299
DM fixed allocation words for Modbus-RTU Easy Master for serial port 2: D32300 to D32399
Instruction-related Information
Background Execution Information
Name
Address
Description
Access
Updated
Serial Port 1 Modbus-RTU
Master Execution Bit
A641.00
Turn ON this bit to send a command and receive a
response for serial port 1 using the Modbus-RTU easy
master function.
This bit will be turned OFF automatically by the system
when communications have been completed.
Turned ON: Execution started
ON: Execution in progress.
OFF: Not executed or execution completed.
Read-only
Serial Port 1 Modbus-RTU
Master Execution Normal
Flag
A641.01
ON when one command has been sent and the
response received for serial port 1 using the Modbus-
RTU easy master function.
ON: Execution normal.
OFF: Execution error or still in progress.
Read-only
Serial Port 1 Modbus-RTU
Master Execution Error Flag
A641.02
ON when an error has occurred in communications for
serial port 1 using the Modbus-RTU easy master func-
tion. The error code is output to D32352 in the DM fixed
allocation words for Modbus-RTU Easy Master.
ON: Execution error.
OFF: Execution normal or still in progress.
Read-only
Serial Port 2 Modbus-RTU
Master Execution Bit
A640.00
Turn ON this bit to send a command and receive a
response for serial port 2 using the Modbus-RTU easy
master function.
This bit will be turned OFF automatically by the system
when communications have been completed.
Turned ON: Execution started
ON: Execution in progress.
OFF: Not executed or execution completed.
Read-only
Serial Port 2 Modbus-RTU
Master Execution Normal
Flag
A640.01
ON when one command has been sent and the
response received for serial port 2 using the Modbus-
RTU easy master function.
ON: Execution normal.
OFF: Execution error or still in progress.
Read-only
Serial Port 2 Modbus-RTU
Master Execution Error Flag
A640.02
ON when an error has occurred in communications for
serial port 2 using the Modbus-RTU easy master func-
tion. The error code is output to D32252 in the DM fixed
allocation words for Modbus-RTU Easy Master.
ON: Execution error.
OFF: Execution normal or still in progress.
Read-only
Name
Address
Description
Access
Updated
Step Flag
A200.12
ON for one cycle when step execution is started with
STEP(008).
Read-only
Macro Area Input Words
A600 to
A603
Before the subroutine specified in MCRO(099) is exe-
cuted, the source words for the subroutine are trans-
ferred to A600 through A603 (input parameter words).
Read/write
Macro Area Output Words
A604 to
A607
After the subroutine specified in MCRO(099) has been
executed, the results of the subroutine are transferred
from A604 through A607 to the specified destination
words (output parameter words).
Read/write
Name
Address
Description
Access
Updated
DR00 Output for Back-
ground Execution
A597
When a data register is specified as the output for an
instruction processed in the background, A597 receives
the output instead of DR00.
0000 to FFFF hex
Read-only
IR00 Output for Background
Execution
A595 and
A596
When an index register is specified as the output for an
instruction processed in the background, A595 and A596
receive the output instead of IR00.
0000 0000 to FFFF FFFF hex
(A595: Rightmost digits, A596: Leftmost digits)
Read-only
Содержание CP1H CPU UNITS - PROGRAMMING 05-2007
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Страница 370: ...336 Analog I O XA CPU Units Section 5 5...
Страница 552: ...518 Trouble Shooting Section 8 7...
Страница 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 598: ...564 Sample Application Section 9 12...
Страница 642: ...608 Standard Models Appendix A...
Страница 643: ...609 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 652: ...618 Dimensions Diagrams Appendix B...
Страница 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Страница 776: ...742 PLC Setup Appendix G...
Страница 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Страница 786: ...752 Revision History...