93
Computing the Cycle Time
Section 2-7
4: I/O Refreshing
5: Peripheral Servicing
Details
Processing time and fluctuation cause
CPU Unit built-
in I/O and I/O
on CP-series
Expansion
Units and
Expansion I/O
Units
Outputs from the CPU Unit to the actual
outputs are refreshed first for each Unit,
and then inputs.
I/O refresh time for each Unit multiplied by the number of
Units used.
CJ-series Spe-
cial I/O Units
Words allocated in CIO Area
I/O refresh time for each Unit multiplied by the number of
Units used.
Unit- specific
data
Example: CompoBus/S
remote I/O
CJ-series CPU
Bus Units
Words allocated in CIO and DM Areas
I/O refresh time for each Unit multiplied by the number of
Units used.
Unit- specific
data
Examples:
• Data links for Control-
ler Link Units
• DeviceNet remote I/O
• Send/receive data for
protocol macros
• Socket services for
specific control bits for
Ethernet Units
Details
Processing time and fluctuation cause
Services events for CJ-series Special I/O
Units.
Note
Peripheral servicing does not include
I/O refreshing,
If a uniform peripheral servicing time hasn’t been set in the PLC Setup for
this servicing, 4% of the previous cycle’s cycle time (calculated in step (3))
will be allowed for peripheral servicing.
If a uniform peripheral servicing time has been set in the PLC Setup, servic-
ing will be performed for the set time. Servicing will be performed for at
least 0.1 ms, however, whether the peripheral servicing time is set or not.
If no Units are mounted, the servicing time is 0 ms.
Services events for CJ-series CPU Bus
Units.
Note
Peripheral servicing does not include
I/O refreshing.
Services USB port.
If a uniform peripheral servicing time hasn’t been set in the PLC Setup for
this servicing, 4% of the previous cycle’s cycle time (calculated in step (3))
will be allowed for peripheral servicing.
If a uniform peripheral servicing time has been set in the PLC Setup, servic-
ing will be performed for the set time. Servicing will be performed for at
least 0.1 ms, however, whether the peripheral servicing time is set or not.
If the ports are not connected, the servicing time is 0 ms.
Services serial ports
Services communications ports.
If a uniform peripheral servicing time hasn’t been set in the PLC Setup for
this servicing, 4% of the previous cycle’s cycle time (calculated in step (3))
will be allowed for peripheral servicing.
If a uniform peripheral servicing time has been set in the PLC Setup, servic-
ing will be performed for the set time. Servicing will be performed for at
least 0.1 ms, however, whether the peripheral servicing time is set or not.
If no communications ports are used, the servicing time is 0 ms.
Services built-in flash memory access.
If a uniform peripheral servicing time hasn’t been set in the PLC Setup for
this servicing, 4% of the previous cycle’s cycle time (calculated in step (3))
will be allowed for peripheral servicing.
If a uniform peripheral servicing time has been set in the PLC Setup, servic-
ing will be performed for the set time. Servicing will be performed for at
least 0.1 ms, however, whether the peripheral servicing time is set or not.
If there is no access, the servicing time is 0 ms.
Serves Memory Cassette access.
Содержание CP1H CPU UNITS - PROGRAMMING 05-2007
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Страница 370: ...336 Analog I O XA CPU Units Section 5 5...
Страница 552: ...518 Trouble Shooting Section 8 7...
Страница 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 598: ...564 Sample Application Section 9 12...
Страница 642: ...608 Standard Models Appendix A...
Страница 643: ...609 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 652: ...618 Dimensions Diagrams Appendix B...
Страница 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Страница 776: ...742 PLC Setup Appendix G...
Страница 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Страница 786: ...752 Revision History...