566
Program Transfer
Section 10-1
10-1 Program Transfer
The CX-Programmer is used to transfer the programs, PLC Setup, I/O mem-
ory data, and I/O comments to the CPU Unit with the CPU Unit in PROGRAM
mode. The following procedure is used.
1,2,3...
1.
Select
PLC - Transfer - To PLC.
The Download Options Dialog Box will be
displayed.
2.
Specify the items to transfer.
3.
Click the
OK
Button.
Note
The program data on a Memory Cassette can be automatic transferred when
the power is turned ON.
10-2 Trial Operation and Debugging
10-2-1 Forced Set/Reset
The CX-Programmer can force-set (ON) or reset (OFF) specified bits in the
CIO Area, Auxiliary Area, and HR Area, as well as timer/counter Completion
Flags. Forced status will take priority over status output from the program or
I/O refreshing. This status cannot be overwritten by instructions, and will be
stored regardless of the status of the program or external inputs until it is
cleared from the CX-Programmer.
Force-set/reset operations are used to force input and output during a trial
operation or to force certain conditions during debugging.
Force-set/reset operations can be executed in either MONITOR or PRO-
GRAM modes, but not in RUN mode.
Note
Turn ON the Forced Status Hold Bit (A500.13) and the IOM Hold Bit (A500.12)
at the same time to retain the status of bits that have been force-set or reset
when switching the operating mode.
Turn ON the Forced Status Hold Bit (A500.13) and the IOM Hold Bit
(A500.12), and set the Forced Status Hold Bit at Startup parameter in the PLC
Setup to retain the status of the Forced Status Hold Bit hold to retain the sta-
tus of bits that have been force-set or reset when turning OFF the power.
The following areas can be force-set and reset: CIO Area (I/O bits, data link
bits, CPU Bus Unit bits, Special I/O Unit bits, and work bits), Work Area, Timer
Completion Flags, HR Area, Counter Completion Flags.
CX-Programmer Operation
• Selecting bits for forced setting/resetting
• Selecting forced set or forced reset status
• Clearing forced status (also clearing all forced status at the same time)
Input ignored
CPU Unit
Forced ON regardless
of programming
Forced
set
Forced
set
Program
Содержание CP1H CPU UNITS - PROGRAMMING 05-2007
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Страница 370: ...336 Analog I O XA CPU Units Section 5 5...
Страница 552: ...518 Trouble Shooting Section 8 7...
Страница 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 598: ...564 Sample Application Section 9 12...
Страница 642: ...608 Standard Models Appendix A...
Страница 643: ...609 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 652: ...618 Dimensions Diagrams Appendix B...
Страница 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Страница 776: ...742 PLC Setup Appendix G...
Страница 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Страница 786: ...752 Revision History...