Wiring CP1H CPU Units
Section 3-4
3-4-1
Wiring Power Supply and Ground Lines
CPU Units with AC Power Supply
Wiring the AC Power Supply and Ground Lines
• Wire a separate circuit for the power supply circuit so that there is no volt-
age drop from the inrush current that flows when other equipment is
turned ON.
• When several CP1H PLCs are being used, it is recommended to wire the
PLCs on separate circuits to prevent a voltage drop from the inrush cur-
rent or incorrect operation of the circuit breaker.
• Use twisted-pair power supply cables to prevent noise from the power
supply lines. Adding a 1:1 isolating transformer reduces electrical noise
even further.
• Consider the possibility of voltage drops and the allowable current, and
always use thick power lines.
• Use round crimp terminals for AC power supply wiring.
• AC Power Supply
Provide a power supply of 100 to 240 VAC.
• Use a power supply within the following voltage fluctuation range.
Note
(1) Before connecting the power supply, make sure that the CPU Unit re-
quires an AC power supply and not a DC power supply. The CPU Unit's
internal circuitry will be damaged if AC power is mistakenly supplied to a
CPU Unit that requires a DC power supply.
(2) The power supply input terminals are at the top of the CPU Unit; the ter-
minals at the bottom of the CPU Unit output 24-VDC power for external
devices. The CPU Unit's internal circuitry will be damaged if AC power is
mistakenly supplied to a CPU Unit's power supply output terminals.
!Caution
Tighten the terminal block screws for the AC power supply to the torque of
0.5 N·m. Loose screws may result in fire or malfunction.
• Always ground the ground terminal to 100
Ω
or less to protect against
electric shock and incorrect operation from electrical noise.
MCCB
S
R
L1
L2/N COM
01
03
05
07
09
11
01
03
05 07
09
11
00
02
04
06
08
10
00
02
04
06
08
10
100 to 240 VAC at 50/60 Hz
Upper terminal block
Ground (100
Ω
or less)
GR: Protective ground terminal
LG: Functional ground terminal
Power supply voltage
Allowable voltage fluctuation range
100 to 240 VAC
85 to 264 VAC
6.2 mm max.
Содержание CP1H CPU UNITS - PROGRAMMING 05-2007
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised March 2009...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 174: ...140 CP series Expansion I O Unit Wiring Section 3 6...
Страница 370: ...336 Analog I O XA CPU Units Section 5 5...
Страница 552: ...518 Trouble Shooting Section 8 7...
Страница 595: ...561 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 598: ...564 Sample Application Section 9 12...
Страница 642: ...608 Standard Models Appendix A...
Страница 643: ...609 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 652: ...618 Dimensions Diagrams Appendix B...
Страница 745: ...711 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 746: ...712 Connections to Serial Communications Option Boards Appendix F...
Страница 776: ...742 PLC Setup Appendix G...
Страница 778: ...744 Specifications for External Power Supply Expansion Appendix H...
Страница 786: ...752 Revision History...