ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration
Mode
63
997-263, Issue 4
September 2002
Each of the CBE Output Rules have various configurable
states available, dependent on the rule type. These states
are described below:
a.
Filter-by-type
- options are ANY (all types), OTI
(Optical, Thermal, Ionisation or MULTI sensor), AVS
(ID60 only - see
Appendix 3
), MCP (manual call
point), MON (monitor module). Extinguishing System
options are Smoke/Heat, Sensor/MCP, VIEW/Sensor,
Any Two Zones, Any Two Sensors, Any Single Sensor
and Any Single Module. Output will only operate if the
input is received from a device of the selected type.
b.
Evacuate (EV)
- has two options Yes (Y) or No (N). If
set to Y(es) assigned outputs activate when the END
DELAYS/EVACUATE pushbutton is operated. Outputs
will not operate when this option is set to N(o).
c.
Silenceable (SL)
- has two options Yes (Y) or No (N).
If set to Y(es) assigned outputs will silence when the
SILENCE / RESOUND pushbutton is operated. If set
to N(o) the outputs will only silence after being
activated when the RESET pushbutton is operated.
d.
Interruptable (IN)
- has two options Yes (Y) or No (N).
If set to Y(es) operating the END DELAYS/EVACUATE
pushbutton cancels currently operating delays and
assigned outputs activate. If set to N(o), delays are
NOT interruptable. The delays can only be cancelled
by another qualifying alarm condition. This
configuration does not comply with EN54 regulations.
e.
Class Change (Cl)
- has two options, Yes (Y) or No
(N). If digital input 1 is set to Class Change (see
Section 5.5.16
) and the CBE Class Change option is
set to Y(es), then the assigned outputs operate when
digital input 1 is made. If set to N(o), digital input 1 (set
to Class Change) does not operate the assigned outputs.
f.
Two Zone (Tz)
- has two options Yes (Y) and No (N).
If set to Y(es), at least two zones must be active before
the CBE rule is triggered.
g.
Zones
- determines the output response to fire or plant
alarms on a zone by zone basis using two options:
Zones 01 to 16 and Zones 17 to 32.
i Zones 01 to 16 - addresses the Fire rule silence
options. Each zone can be configured as:
N(o) - the zone is NOT included in the CBE Rule,
outputs will NOT be activated.
Y(es) - the zone is included in the CBE Rule. An alarm
in this zone activates the outputs immediately.
(D)elay - the zone is included in the CBE Rule. An
alarm in this zone will activate outputs after a delay.
Not available for Fire rules if Two Zone is selected.
Extinguishing System rules default to Delay.
(C)oincidence - the zone is included in the CBE Rule.
Two alarms in this zone will activate outputs.
EN54-2 : 7.11.d.
Configured delays MUST
be set to interruptable
(Y) to remain EN54
compliant