ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration
Mode
54
997-263, Issue 4
September 2002
5.6.1.2 Sensor Sensitivity Setting
This option allows the sensitivity of sensors to be changed
during device configuration. Access is via the Circuit
menu. Individual sensor Alarm and/or Day settings can
be changed.
Note:
The
ID60 Panel
supports VIEW
TM
. The procedure
for changing this sensors sensitivity is different,
see
Appendix 2, ID60 Single Loop Panel
Differences
.
During configuration of the sensor sensitivity values, the
LCD returns to the previously configured value if any of
the following occurs:
a. The
4
button on the numeric keypad is pressed.
b. The panel state is unchanged for 1 minute.
c. A value outside the predefined operating limits (80%
to 120%) is entered.
To change the sensor sensitivity settings:
1
At the sensor attributes menu, press the
3
button
on the numeric keypad to display the Sensor Sensitivity
Setting menu:
2
Using the numeric keypad, press
1
to select the
Alarm Sensitivity setting or press
2
to select the
Day Mode Sensitivity setting.
3
At the appropriate prompt, use the numeric keypad to
enter the desired percentage value.
4
Press
5
to confirm the value entered or press
4
repeatedly to cancel the operation.
[Sensor nn - AAA]
Sensitivity
Enter new alarm level : ____
< : Cancel
[Sensor nn - AAA]
Sensitivity
1 : Alarm(100%)
2 : Day(100%)
< : Cancel
[Sensor nn - AAA]
Sensitivity
Enter day mode alarm : ____
< : Cancel
[Sensor nn - AAA]
Sensitivity
1 : Alarm(120%)
2 : Day(80%)
< : Cancel
or
2
1
1
2