ID50 Series Panel - Installation, Commissioning & Configuration Manual
Appendix 1 - S
pecifications
A1 - 3997-263
, Issue 4
September 2002
External Connections:
Cable entry:
16 x 20mm knock-outs in top of
cabinet.
Terminals:
All external connections made
through screw terminals, each of
which will accept cable sizes
between 0.5mm
2
and 2.5mm
2
.
Electrical:
Classification:
Installation Class 1, (panel must be
earthed).
Panel Ratings
Unloaded:
Quiescent:
90mA
Alarm:
110mA
Fully Loaded:
Quiescent:
950mA (includes 0.48A Max.
Battery Charge Current)
Alarm:
1.5A
Power Supply Unit (PSU)
Input Ratings:
Supply Rating:
230VAC ± 15%, 50Hz, 1.0A
Fuse Rating (MF1):
T 2A 250V H Ceramic.
Batteries:
Internal batteries:
Two 12V, 12Ah sealed, lead-acid
types MUST be used.
Note:
Battery lifetime depends on the ambient temperature;
refer to the battery manufacturers technical
specification for guidance. (Refer to Panel Ratings -
Fully Loaded for charger limitations).
Maximum battery ratings: 12Ah