ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration
Mode
50
997-263, Issue 4
September 2002
5.5.23 VdS Compatibility
The VdS Compatibility option must be set to Disabled.
1
From the Commissioning menu, using the numeric
keypad press the
1
button to enter the Setup menu.
2
Press the
2
/
8
buttons to step through the Setup
menus until the VdS Compatibility menu is displayed.
3
If necessary, press the
6
button to change VdS
Compatibility from ENABLED to DISABLED.
4
Press
4
to return to the Commissioning menu. All
changes will be saved on exiting this menu.
To disable this function
1
To disable Auto High Test, press the
1
button:
2
Press
4
to return to the Commissioning menu.
5.5.22 Diagnostic Mode
The Diagnostic Mode option allows extended fault and
fire reporting and determines whether events are
suppressed until confirmed. To enable Diagnostic Mode:
1
From the Commissioning menu, using the numeric
keypad press the
1
button to enter the Setup menu.
2
Press the
2
/
8
buttons to step through the Setup
menus until the Diagnostic Mode menu is displayed.
3
Press the
6
button to select the required setting,
either ON or OFF.
4
Press
4
to return to the Commissioning menu. All
changes will be saved on exiting this menu.
[Setup]
Auto High Test = DISABLED
> : Change
1 : Disable
×
: More
< : Exit
[Setup]
Auto High Test = 07:46
> : Change
1 : Disable
×
: More
< : Exit
[Setup]
Diagnostic Mode = ON
> : Change
×
: More
< : Exit
[Setup]
Diagnostic Mode = OFF
> : Change
×
: More
< : Exit
[Setup] Language =
English
> : Change
×
: More
< : Exit
1
1
or
8
2
6
[Setup] Language =
English
> : Change
×
: More
< : Exit
1
or
8
2
6
[Setup]
VdS Compatibility =
DISABLED
> : Change
×
: More
< : Exit