ID50 Series Panel - Installation, Commissioning & Configuration Manual
Appendix 2 - ID60 Panel Differences
A2 - 3
997-263, Issue 4
September 2002
A2.2 Learning Individual VIEW
TM
Sensors
When installed on a loop from the
ID60 Panel
, each
VIEW
TM
sensor is assigned the Advanced VIEW
TM
Sensor
(AVS) type by default. This may then be configured as
Advanced VIEW
TM
Reference (AVR) type.
A VIEW
TM
sensor may be learnt in the same manner as
any sensor but has an additional Type configuration
option. The procedure to configure the sensor type is as
follows:
1
Using the numeric keypad, press
1
to select the
sensors configuration option.
2
At the prompt, using the numeric keypad enter the
address of the VIEW
TM
sensor to be edited and confirm
using
5
.
3
The LCD then shows current settings and editable
parameters. Using the numeric keypad, press
2
to
select the Type option.
Note:
Use
2
/
8
to select the next/previous address
respectively.
4
The LCD then displays the VIEW
TM
device type
selection menu. Using the numeric keypad, press
1
or
2
to select the AVS or AVR type respectively.
The display automatically returns to the previous
menu, as shown below:
[S1 Device] 1 : Sensors
2 : Modules
[Sensor nn - AVS] 1 : Zone (nn)
2 : Type
3 : Sensitivity
4 : [
Blank/Existing Text
]
[Sensor]
Enter Address ____
[Sensor nn - AVR] 1 : Zone (nn)
2 : Type
3 : Sensitivity
4 : [
Blank/Existing Text
]
[Sensor nn - AVS]
Select Type :
1 : AVS
2 : AVR
< : Cancel
1
2
or
1
2