ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration
Mode
55
997-263, Issue 4
September 2002
5.6.1.3 Type Setting
Standard input modules in zones 1 to 16 can be assigned
to various types as shown below. A Manual Call Point
(MCP) input has the action of a zone fire alarm Manual
Call Point with prioritized polling. A Fire Alarm Monitor
(MON) input has the action of a zone fire alarm with non-
prioritized polling. An input module assigned to a zone in
the range 17 to 32 is automatically given the type AUX,
for a plant alarm input.
Input devices of type AUX can be programmed for plant
alarm, reset panel, silence sounders, mute buzzer, class
change, (only used when Class Change input has been
configured for Day Mode start), abort switch and hold
switch (the last two cases are associated with the
configuration of Extinguishing System inputs).
The device type is configured during the learn process.
Sensor types and Plant Warning inputs (AUX) cannot be
changed. The Type menu option is not shown on the
display for these devices.
Monitored output modules can be assigned to various
types as shown below.
To change the module type as displayed on the LCD:
1
Using the numeric keypad press
2
(Type option)
from the menu displaying the module attributes:
2
Selecting the Type option displays one of the following:
Note:
On-Board circuit 1 ONLY supports SDR, CTL and
TxD Monitored Output Circuits. On-Board circuit 2
ONLY supports SDR and CTL Monitored Output
Circuits. On-Board circuits 3 and 4 support all
Monitored and Unmonitored Output Circuits if
Jumper Links J1 and J2 have been correctly
configured. On-Board circuits 5 and 6 are fixed as
Unmonitored Output circuits (RLY).
3
Select the module type and using the numeric keypad
press the corresponding number,
1
,
2
,
3
,
4
,
5
or
6
to select the new type. The LCD
then displays the new module attributes menu. A
typical menu is shown below:
[Module nn - MCP] 1 : Zone (nn)
2 : Type
4 : [
Blank/Existing Text
]
[Module nn - SDR] 1 : Zone (nn)
2 : Type
3 : CBE Rule (nn) 4 : [
Blank/Existing Text
]
[Module nn - MCP] 1 : Zone (nn)
2 : Type
4 : [
Blank/Existing Text
]
2
2
1
3
4
EN54-2 : 7.6.1, 7.8
Level 2 Keyswitch access
MUST be used with an input
Type AUX panel Reset (7.6.1)
& Silence/Resound (7.8).
[Module nn - SDR] Select Type :
1:SDR 2:CTL3:RLY 4:EST 5:ESO 6:ESM <:Cancel
[Module nn - MCP] Select Type :
1:MCP 2:DKM 3:MON 4:MNS 5:MRL6:IRL <:Cancel
6
5
The first 30 modules (from
lowest address upwards)
restricted to types MCP, DKM,
MRL, IRL and all AUX actions
except Plant Alarm, are added
automatically to a priority poll
list. Subsequent modules are
polled normally.