ID50 Series Panel - Installation, Commissioning & Configuration Manual
Appendix 1 - S
pecifications
A1 - 2
997-263, Issue 4
September 2002
Environmental:
Climatic classification: 3K5, (IEC 721-2-3)
Operating temperature: -5
o
C to +45
o
C,
(recom5
o
C to 35
o
C)
Humidity:
5% to 95% R.H.
Height above sea level: Maximum, 2000m
Panel sealing:
IP 30, (EN 60529)
Vibration:
EN 60068-2-6, 10-150Hz at
0.981ms
-2
(Meets the requirements
of EN 54-2/4)
EMC:
Emissions:
EN 50081-1
Immunity:
EN 50130-4
Safety:
EN 60950
Displays and Indications:
Alphanumeric display: 2 line x 40 character, backlit LCD.
LED Status Indicators: DISABLEMENT, TEST, BUZZER
MUTED, PLANT ALARM, DELAYED
MODE, RELAY DISABLE, POWER,
FAULT, POWER SUPPLY FAULT,
EARTH FAULT, SYSTEM FAULT,
SOUNDER FAULT, SOUNDERS
DISABLED, SOUNDERS SILENCED.
Zone Indicators:
Individual FIRE and Fault/Disable/
Test indicators for 16 zones.
Controls:
Dedicated flush
pushbuttons are provided
for the following functions: RESET, MUTE BUZZER, SILENCE/
RESOUND,
END DELAYS/
EVACUATE.
Additional pushbuttons for
configuration and selection
of software functions:
2
4
6
8
KEYS
5
KEY
0..9
KEY
KEY
10 BUTTON NUMERIC KEYPAD
System Capacity:
Number of loops:
1
Number of zones:
32 (16 Fire + 16 Plant Alarm)
Devices per loop:
99 sensors + 99 modules or
99 sensors + combination of up
to 99 modules/sounders within
strict limits.
Содержание ID50 SERIES