ID50 Series Panel - Installation, Commissioning & Configuration Manual
Appendix 2 - ID60 Panel Differences
A2 - 4
997-263, Issue 4
September 2002
A2.3 Changing VIEW
TM
Sensor Sensitivity
The following procedure describes how to configure the
sensitivity levels for alarm (alarm and pre-alarm), day
(alarm and pre-alarm) and sensor grouping for a VIEW
TM
sensor.
1
Follow the procedure in
Section A2.2, Learning
Individual VIEW
TM
Sensors
to access the sensor
configuration menu. The LCD shows current settings
and editable parameters. Using the numeric keypad,
press
3
to select the Sensitivity option.
Note:
Use the
2
/
8
buttons to select the previous/
next address respectively.
2
The LCD then displays the VIEW
TM
sensor Sensitivity
menu. The sensitivity is displayed as two values in
brackets. The first signifies the alarm level (default
L5), and the second the pre-alarm level (default 5).
3
To change the Alarm; Day or AVSGroup options,
using the numeric keypad press
1
,
2
or
3
respectively. If
1
(Alarm) is pressed the LCD
prompts for a new alarm level as follows:
4
Using the numeric keypad enter the required alarm
value 1 to 9, and press
5
to confirm. The LCD then
automatically prompts for the pre-alarm value as
follows:
5
Enter the required prealarm value 0 to 9, and press
5
to confirm. The LCD then automatically returns
to the VIEW
TM
sensor Sensitivity menu.
Day Mode Levels
The Day option alarm levels are changed in the same
manner as the Alarm option.
Using the numeric keypad, press
2
to access the Day
option, then follow the procedure above.
[Sensor nn - AVS] 1 : Zone (nn)
2 : Type
3 : Sensitivity
4 : [
Blank/Existing Text
]
[Sensor nn - AVS]
Sensitivity
1 : Alarm(L5,5) 2 : Day(L5,5) 3 : AVSGroup(01)
[Sensor nn - AVS]
Sensitivity
Enter new alarm level : ____
< : Cancel
[Sensor nn - AVS]
Sensitivity
Enter new prealarm level : ____
< : Cancel
1
3