ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration
Mode
69
997-263, Issue 4
September 2002
5.7.7 Two Zone
The Two Zone option has two states, Yes (Y) and No (N).
This option is available with the Fire, Pre-Alarm and Plant
Warning rules. To change the Two Zone rule setting:
1
Press the
7
button (using the numeric keypad) to
select the pattern Two Zone option from the menu
below.
2
Press the
6
button to select the required setting.
Refer to
Section 5.7, Control-By-Event Output
Rules
for further information.
3
Confirm the selection by pressing the
5
button. To
cancel the selection, press
4
. In either case the
menu below is re-displayed.
CBE Rule:01
6:Class Change
7:Two Zone
9:Zones
×
: More
CBE Rule:01
Two Zone = [N]
>:Change
3
:Accept
< : Cancel
CBE Rule:01
Two Zone = [Y]
>:Change
3
:Accept
< : Cancel
CBE Rule:01
6:Class Change
7:Two Zone
9:Zones
×
: More
6
5
7