ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration
Mode
53
997-263, Issue 4
September 2002
5.6.1.1 Zone Setting
This option is used during manual configuration to assign
a specific device to a specific zone. The option is
accessed from the Commissioning Menu.
A maximum of 32 possible zones can be configured,
consisting of 16 Fire alarm zones (1 to 16) and 16
secondary zones (17 to 32). The secondary zones are
used for AUX plant alarm and warning inputs. Device
types SND, RLY, CTL, EST and ESO can be in any zone.
To change the zone of a specified sensor or module,
selection of either sensors or modules at the Devices
menu is first required. If sensors are selected, the display
prompts for zone editing, as follows;
1
From the menu displaying the device attributes, press
the
1
button on the numeric keypad to access the
Zone Setting menu:
2
Using the numeric keypad, enter the required zone
number between 1 and 16 and confirm using the
5
button.
If the entered number is out of the permissible range,
the zone number reverts to that previously allocated.
To-enter the zone number or press
4
to cancel.
Note:
Standard input modules can be assigned to any of
the 32 zones. Conventional detector input modules
(ZMX) can be assigned to zones 1 to 16 only. When
an input module is assigned to a zone in the range
1 to 16, it is given the default type MCP for a Manual
Call Point. When an input module is assigned to a
zone in the range 17 to 32, it is given the default
type AUX for plant alarm input.
Section 5.6.1.3,
Type Setting
describes how to select the input type.
Output modules can be assigned to any of the 32
zones for fault reporting. The operation of the
output depends on the CBE Rule to which the
module is assigned.
Fire Inputs can only be
assigned to
Zones 1 to 16
[Sensor nn - AAA] 1 : Zone (nn)
3 : Sensitivity
4 : [
Blank/Existing Text
]
[Sensor nn - AAA] 1 : Zone (nn)
Enter New Zone = ____
< : Cancel
[Sensor nn - AAA] 1 : Zone (nn)
Enter New Zone = 01
< : Cancel
1
The procedure for
changing the zone of a
module is the same as for
a sensor
[Module nn - AAA] 1 : Zone (nn)
2 : Type
3 : CBE Rule (nn) 4 : [
Blank/Existing Text
]
c. The CBE Rule number. It is NOT possible to change
the configuration of the associated CBE Rule.
d. The device text string (see
Section 5.8, Text Editing
).