ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration
Mode
45
997-263, Issue 4
September 2002
5.5.14 Repeater Protocol
This option is used to select one of two available protocol
formats when repeaters are connected to the panel via
the RS485 communications link. The options available
are:
a. NOTIFIER
b. ARP50/RP50.
The NOTIFIER protocol supports the IDR-2A and IDR-2P
Repeaters.
There are two additional options:
c. Third party equipment connection at the RS485 link.
d. DISABLED, disables communication to any device
connected to the panel.
To change the Repeater Protocol:
1
From the Commissioning menu, press the
1
button
on the numeric keypad to enter the Setup menu.
2
Press the
2
/
8
buttons to scroll through the Setup
menu until the Repeater Protocol menu is displayed.
3
Press the
6
button repeatedly to step through the
alternative protocol settings.
4
Press
4
to return to the Commissioning menu.
[Setup] Language =
English
> : Change
×
: More
< : Exit
[Setup] Repeater Protocol = NOTIFIER
> : Change
×
: More
< : Exit
[Setup] Repeater Protocol = NOTIFIER
> : Change
×
: More
< : Exit
[Setup] Repeater Protocol = ARP50/RP50
> : Change
×
: More
< : Exit
1
or
8
2
6