ID50 Series Panel - Installation, Commissioning & Configuration Manual
Introduction
3
997-263, Issue 4
September 2002
1.4 CE Marking
This panel is CE Marked to show that it conforms to the
requirements of the following European Community
Directives:
n
Electromagnetic Compatibility Directive 89/336/EEC
(and the amending Directives 92/31/EEC, 93/68/EEC)
n
Low Voltage Directive 73/23/EEC (and the amending
Directive 93/68/EEC).
1.5 EN54 Functions
This fire control panel is designed to comply with the
requirements of EN 54 Part 2/4: 1997. In addition to the
basic requirements of EN 54-2, the panel may be configured
to conform with the following optional functions - the
applicable clauses of EN 54-2 are referenced as follows:
Options
Clause
Indications:
Fault signals from points
8.3
Recording of the number of entries
into fire alarm condition
7.13
Controls:
Coincidence detection
7.12
Delay of the immediate actioning of outputs
7.11
Disablement of each address point
9.5
Test condition
10
Outputs:
Fire alarm device(s) (Sounders)
7.8
Fire alarm routing equipment
7.9
Fire protection equipment
7.10
Fault warning routing equipment
8.9
(requires monitoring by fault routing equipment)
The following features are provided by the Power Supply
Unit (PSU) of the ID50 Series Panel to comply with
EN 54-4.
Features of the ID50
EN54-4
Power Supply Unit (PSU)Clause
Derive power from the mains supply5.1
Derive power from a standby battery source
5.2
Charge and monitor the standby
battery/batteries
5.3
Detect and signal various PSU faults
5.4