ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration
Mode
62
997-263, Issue 4
September 2002
5.7 Control-By-Event Output Rules
This menu allows the configuration and viewing of the 64
Control-By-Event (CBE) Output Rules available to the
commissioning engineer. CBE Rules 1 to 5 and 7 are
pre-defined (see below for further information).
Each rule (including those that are pre-defined) can be
modified and applied to On-Board Outputs and loop
Output Modules (e.g. SDR, RLY, CTL). Each output is
referred to as an assigned output. All relevant CBE rule
information is shown on one display, as follows:
a.
A Fire rule. This CBE rule type activates assigned
outputs in response to fire alarms in specified
zones. Individual zones can be modified to
determine the output response.
b.
A Pre-Alarm rule. This CBE rule type activates
assigned outputs in response to a general pre-
alarm condition at the panel.
c.
A Plant Warning rule. This CBE rule type activates
assigned outputs in response to plant alarms in
specified zones. Individual zones can be modified
to determine the output response.
d.
A Fault rule. This CBE Rule type activates assigned
outputs in response to a general fault condition at
the panel.
e.
A Fire Output/Transfer rule. This CBE Rule type
activates assigned outputs in response to the
operation of the Fire Output/Transfer relay.
f.
A Reset rule. This CBE Rule type activates
assigned outputs for 5 secs in response to a panel
reset.
The following rules are not pre-defined. Both are only
selectable via the Change option.
a.
A Device Input rule. Determines the output
response to up to three (3) specified input devices
(modules or sensors). An input from any of the
specified devices will turn on the assigned outputs.
Refer to
Section 5.7.9, CBE Rules: Device Inputs
.
b.
A Day Mode rule. This CBE Rule type activates
assigned outputs when the panel is operating in
Day Mode.
c.
An Extinguishing System rule. This CBE Rule type
activates extinguishing release system(s) in
response to fire alarm inputs in specified zones.
CBE 01 [FIRE
][ANY] 1--------------------16
1 : Change[EvSlln
] YYYYNNYYNDDNCCNN
CBE 02 [PRE-ALARM][ANY]
1 : Change[ Sl
]
CBE 03 [PLANT
]
17-------------------32
1 : Change[
] YYYYNNYYNDDNCCNN
CBE 04 [FAULT
][ANY]
1 : Change
CBE 05 [FTR
]
1 : Change
CBE 07 [RESET
]
1 : Change
CBE nn [INPUTS ]
Dv1 Dv2 Dv3
1 : Change[EvSl
]
S01
---
M05
CBE 08 [DAY MODE]
1 : Change
CBE nn [EXTSYSTEM] Sk Tmr 1- - - - - - - - - - - - - - 16
1 :Change [Smoke/Heat]
YYYYNNYYNDDNNNN