ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration
Mode
66
997-263, Issue 4
September 2002
5.7.2 Filter-by-Type
This option is available with the Fire, Fault, Pre-alarm
and the Extinguishing System rules. The Filter-by-type
option, when used with Fire, Fault and Pre-alarm
categories has five selections: ANY, OTI, AVS, MCP and
MON. The Filter-by-type option, when used with the
Extinguishing System category has seven selections:
Smoke/Heat, Sensor/MCP, VIEW/Sensor, Any Two
Zones, Any Two Sensors, Any Single Sensor and Any
Single Module. Refer to
Section 5.7, Control-by-Event
Output Rules
for further information.
To select the type filter for Fire, Fault or Pre-alarm:
1
Press the
2
button (using the numeric keypad) to
select the Filter option from the menu below.
2
Press the
2
/
8
buttons to select the required filter.
3
Confirm the selection by pressing the
5
button. To cancel
the selection, press
4
button.
To select the type filter for Extinguishing System:
1
Press the
2
button (using the numeric keypad) to
select the Filter option from the menu below.
2
Press the
2
/
8
buttons to select the required filter.
3
Confirm the selection by pressing the
5
button. To cancel
the selection, press
4
button.
CBE Rule:01
1:Type
2:Filter
3:Evac
4:Silence
5:Interrupt
×
: More
CBE Rule:01
Current Filter Type = [ANY]
×
: Change Filter Type
3
: Accept < : Cancel
5
2
or
8
2
CBE Rule: 01 1:Type
2:Filter
8:Soak Timer
9:Zones
CBE Rule:nn
Ext. Filter Type = [One sensor]
×
: Change Filter
3
: Accept
< : Cancel
5
2
or
8
2