4-2
Power-up procedure
411-2051-500
Draft
00.01
November 1999
Voltage checks
This entire procedure is used for installation and commissioning only.
Figure 5-2 shows the DC breaker assignments on the RIPs. The breakers and
the common ground bar distribute the power/grounding to the individual
shelves through cables that exit out connectors in each side of the RIP. The
cables are then routed down each side of the frame.
4
Verify that the breaker positions on the power
bay have been labeled and are cabled as
indicated on the labels.
Note:
See Tables 5-12 to 5-4 for the RIP
breaker panel assignments.
5
Verify that the equipment bays are bonded to
the principle ground bar line-up feeder with a
#6 AWG jumper.
Table 4-1
Minimum bending radii of power cables
Wire Size
Inches
Millimeters
Wire Sizes
Inches
Millimeters
14 AWG
11/16
17.5
3/0 AWG
3 3/16
80.5
12 AWG
3/4
19.6
4/0 AWG
3 7/16
87.6
10 AWG
15/16
23.1
300 MCM
4 1/8
104.6
8 AWG
1 3/16
31.0
350 MCM
4 3/8
111.5
6 AWG
1 1/2
39.6
400 MCM
4 5/8
117.3
4 AWG
1 3/4
45.7
500 MCM
5 1/16
128.3
2 AWG
2 1/8
53.3
600 MCM
5 9/16
142.2
1 AWG
2 1/2
63.0
700 MCM
5 15/16
151.1
1/0 AWG
2 5/8
68.0
750 MCM
6 1/8
155.4
2/0 AWG
2 7/8
73.9
800 MCM
6 5/16
160.0
Step
Action
Observation
Содержание DualMode 800
Страница 2: ......
Страница 4: ......
Страница 6: ...vi Publication history Nortel Networks Confidential 411 2051 500 Draft 00 01 November 1999...
Страница 82: ...2 20 Periodic maintenance 411 2051 500 Draft 00 01 November 1999...
Страница 90: ...3 8 Test equipment and precautions 411 2051 500 Draft 00 01 November 1999...
Страница 100: ...5 6 Master Oscillator tests 411 2051 500 Draft 00 01 November 1999...
Страница 106: ...6 6 Antenna and transmission line tests 411 2051 500 Draft 00 01 November 1999...
Страница 116: ...8 4 Alarm Control Unit ACU tests 411 2051 500 Draft 00 01 November 1999...
Страница 138: ...10 2 ICRM tests 411 2051 500 Draft 00 01 November 1999...
Страница 200: ...12 10 Enclosure maintenance 411 2051 500 Draft 00 01 November 1999...
Страница 208: ...A 8 Appendix A Frequency table 411 2051 500 Draft 00 01 November 1999...
Страница 215: ......