Nortel Networks Confidential
Alarm Control Unit
1-7
Wireless Solutions
DualMode 800 Enclosure Maintenance Manual
MTX08
Figure 1-4
Typical Output Monitor screen display
Note: An Urban cell site does not have specific assignment for output
contact points.
HH:MM is the ACU clock display. The display updates the time once every
minute.
The status of each point is displayed as follows (see Figure 1-4 for the screen
display):
•
Open
The output contact is open.
•
Closed
The output contact is closed.
You can monitor the status of the output contacts continuously because the
terminal updates the display with an opened or closed output contact.
After you leave the Monitor function, the data will still be displayed until you
press the RETURN key.