8-1
Wireless Solutions
DualMode 800 Enclosure
Maintenance Manual
MTX08
Alarm Control Unit (ACU) tests
8
Overview
The Alarm Control Unit (ACU) provides discrete alarm monitoring, reporting
and control functions at a cell site. The site ACU concentrates all alarm input
points at the cell site and updates the MTX of any status change over
redundant data links. The MTX can also poll for the condition of the ACU
and request current status information or change the status of any output
control contact. For a complete description of the ACU, refer to the
DualMode 800 Enclosure Functional Description, 411-2051-100.
Alarm Control Unit test setup
Connect a VT100 terminal (or equivalent) using a null modem cable to the
ACU local terminal connector.
Step
Action
Observation
1
Set up the terminal as per the requirements
to the right.
BAUD Rate:
TX 9600
RX 9600
Scroll:
smooth
Auto repeat:
on
ANSI
Auto Wrap:
off
Receiver Parity:
ignore
Parity:
disabled
Character Bits:
8 bits
Interface:
on
Scroll Key:
VT100
Form Feed:
line feed
Control Characters:
executed
Local Echo:
off
RTS-CTS Handshake: off
8 Bits Tx:
space
- continued -
Содержание DualMode 800
Страница 2: ......
Страница 4: ......
Страница 6: ...vi Publication history Nortel Networks Confidential 411 2051 500 Draft 00 01 November 1999...
Страница 82: ...2 20 Periodic maintenance 411 2051 500 Draft 00 01 November 1999...
Страница 90: ...3 8 Test equipment and precautions 411 2051 500 Draft 00 01 November 1999...
Страница 100: ...5 6 Master Oscillator tests 411 2051 500 Draft 00 01 November 1999...
Страница 106: ...6 6 Antenna and transmission line tests 411 2051 500 Draft 00 01 November 1999...
Страница 116: ...8 4 Alarm Control Unit ACU tests 411 2051 500 Draft 00 01 November 1999...
Страница 138: ...10 2 ICRM tests 411 2051 500 Draft 00 01 November 1999...
Страница 200: ...12 10 Enclosure maintenance 411 2051 500 Draft 00 01 November 1999...
Страница 208: ...A 8 Appendix A Frequency table 411 2051 500 Draft 00 01 November 1999...
Страница 215: ......