3.4.1 Resistive Programming
Resistive programming requires connection of an external potentiometer or resistors between
terminals 21, 3, and 1 of JS1. Terminal 21 is a 10.0 V precision reference, terminal 1 is the
reference ground, and terminal 3 is the voltage set point input. Like front panel rotary control,
the precision reference produces a voltage across the potentiometer or resistors which is then
used to produce the voltage set point. Metal film resistors or a wire wound potentiometer will
result in the lowest temperature coefficient.
The current set point, over voltage trip, and over current trip can be programmed in the same
manner. Referring to the Table 3.1 for terminal identification, use terminal 22 to program the
current set point, terminal 4 to program over voltage trip, and terminal 23 to program over
current trip. The power supply has been calibrated to produce full scale output voltage and
current with 10.0 V inputs at the external reference input terminals. Furthermore, over voltage
and over current trip have been calibrated to trip at 110% full scale output voltage and current
with 10.0 V inputs at the external reference input terminals.
If the applied voltage at any input is greater than 12.50 V, the pgl (program line) LED will light
and the power supply will turn off.
Table 3.1
EXTERNAL PROGRAMMING PARAMETERS
TERM
PARM
DESCRIPTION
INPUT
RANGE (V)
OUTPUT
RANGE
3
22
4
23
VREF EXT
IREF EXT
TVREF EXT
TIREF EXT
Voltage Set
Current Set
Over Voltage Trip Set
Over Current Trip Set
0-10.0
0-10.0
0-10.0
0-10.0
0-100% FS Voltage
0-100% FS Current
0-110% FS Voltage
0-110% FS Current
3.4.2 Voltage Programming
Voltage programming is very similar to resistive programming. In this case, the voltage
reference, terminal 21 of JS1, is not used and an external voltage reference is applied to the
programming inputs directly. A 10.0 V voltage source placed between terminals 3 and 1 of JS1
will produce full scale output voltage.
The current set point, over voltage trip, and over current trip can be programmed in the same
manner. Referring to the Table 3.1 for terminal identification, use terminal 22 to program the
current set point, terminal 4 to program over voltage trip, and terminal 23 to program over
current trip. The power supply has been calibrated to produce full scale output voltage and
current with 10.0 V inputs at the external reference input terminals. Furthermore, over voltage
and over current trip have been calibrated to trip at 110% full scale output voltage and current
with 10.0 V inputs at the external reference input terminals.
If the applied voltage at any input is greater than 12.50 V, the pgl (program line) LED will light
37
Содержание XR III series
Страница 1: ...OPERATING AND SERVICE MANUAL XR SERIES III DC POWER SUPPLIES...
Страница 2: ......
Страница 3: ...MAGNA POWER ELECTRONICS INC 39 ROYAL ROAD FLEMINGTON NJ 08822 February 20 2012...
Страница 4: ......
Страница 88: ...Figure 4 1 Status Byte Generation Figure 4 2 ESE and ESR Generation 76...
Страница 95: ...IEEE Standard CLS ESR ESE STB SRE IDN SAV RCL RST Notes 1 C command Q query 83...
Страница 97: ...Figure 5 1 Configuration setup Figure 5 2 GPIB communications setup 85...
Страница 99: ...Figure 5 4 Virtual Control Panel Figure 5 5 Command Panel 87...
Страница 102: ...Figure 5 7 Calibration Panel Figure 5 8 Firmware Panel 90...
Страница 103: ...Figure 5 9 Modulation Panel 91...
Страница 123: ...Figure B 1 Information Panel Figure B 2 Configure Panel 111...
Страница 124: ...Figure B 3 Reboot in Progress Panel Figure B 4 Web Control Panel 112...