2.0 INSTALLATION AND POWER ON CHECK
XR Series power supplies are intended for rack mount installations only and are designed to fit
in standard 19" equipment racks. Additional support, other than that provided by the front panel,
is required. Angle slides or cross beam supports securely fastened to the rack are recommended
for supporting the weight of the power supply. The unit should be horizontally mounted.
Caution: The power supply is too heavy for one person to safely lift and mount.
To avoid injury, ask a co-worker for assistance.
2.1
Cooling
Each power supply enclosure is cooled by suitable blowers exhausting warm air to the rear of the
cabinet. Fresh air intake is from the sides of the cabinet allowing two or more XR Series
supplies to be stacked. Equipment racks should be equipped with fans or blowers to remove heat
generated by the power supplies. The manufacturer recommends fresh air intake at the bottom
of the cabinet and exhaust at the top. Fans and blowers should be rated at 300 CFM for each XR
Series supply.
Caution: blocking ventilation will cause the power supply to overheat.
2.2
AC Input Connections
Caution: disconnect AC power from the mains before attempting any
installation procedure.
Caution: a safety ground wire must be connected to the unit as indicated by
the protective ground symbol at the rear of the power supply.
AC power is wired to the power supply by attaching three cables plus ground for 3-phase
installations and two cables and ground for single phase installations. The manufacture
recommends cables, as specified in Tables 2.1 or 2.2, be crimped to ring terminals and securely
fastened to the studs at the rear of the power supply. After connections are made, screw the four
standoffs into the back panel and place the protective shield over the connections.
18
Содержание XR III series
Страница 1: ...OPERATING AND SERVICE MANUAL XR SERIES III DC POWER SUPPLIES...
Страница 2: ......
Страница 3: ...MAGNA POWER ELECTRONICS INC 39 ROYAL ROAD FLEMINGTON NJ 08822 February 20 2012...
Страница 4: ......
Страница 88: ...Figure 4 1 Status Byte Generation Figure 4 2 ESE and ESR Generation 76...
Страница 95: ...IEEE Standard CLS ESR ESE STB SRE IDN SAV RCL RST Notes 1 C command Q query 83...
Страница 97: ...Figure 5 1 Configuration setup Figure 5 2 GPIB communications setup 85...
Страница 99: ...Figure 5 4 Virtual Control Panel Figure 5 5 Command Panel 87...
Страница 102: ...Figure 5 7 Calibration Panel Figure 5 8 Firmware Panel 90...
Страница 103: ...Figure 5 9 Modulation Panel 91...
Страница 123: ...Figure B 1 Information Panel Figure B 2 Configure Panel 111...
Страница 124: ...Figure B 3 Reboot in Progress Panel Figure B 4 Web Control Panel 112...