5 - 60
Chapter 5 Data Used for Positioning Control
Pr.54 OPR torque limit value
Set the value to limit the servomotor torque after reaching the creep speed during
machine OPR.
Refer to Section 13.4.2 "Torque limit function" for details on the torque limits.
Pr.55 Operation setting for incompletion of OPR
Set whether the positioning control is executed or not (When the OPR request flag
is ON.).
0: Positioning control is not executed.
1: Positioning control is executed.
(1) When OPR request flag is ON, selecting "0: Positioning control is not
executed" will result in an "Operation starting at incompletion of OPR" error
(error code: 547), and positioning control will not be performed. At this time,
operation with the manual control (JOG operation, inching operation, manual
pulse generator operation) is available.
The positioning control can be executed even if the OPR request flag is ON
when selecting "1: Positioning control is executed".
(2) The following shows whether the positioning control is possible to start/restart
or not when selecting "0: Positioning control is not executed".
(a) Start possible
Machine OPR, JOG operation, inching operation, manual pulse
generator operation, current value changing using current value
changing start No. (9003).
(b) Start/restart impossible control
The positioning control is impossible to start/restart in the following case.
1-axis linear control, 2/3/4-axis linear interpolation control, 1/2/3/4-axis
fixed-feed control, 2-axis circular interpolation control with sub point
designation, 2-axis circular interpolation control with center point
designation, 1/2/3/4-axis speed control, Speed-position switching control
(INC mode/ ABS mode), Position-speed switching control, current value
changing using current value changing (No.1 to 600).
(3) When OPR request flag is ON, starting Fast OPR will result in an “Home
positioning return (OPR) request flag ON” error (error code: 207) despite the
setting value of “Operation setting incompletion of OPR”, and Fast OPR will
not be executed.
CAUTION
Do not execute the positioning control in home position return request signal ON for the axis
which uses in the positioning control.
Failure to observe this could lead to an accident such as a collision.
Содержание MELSEC-Q QD77MS
Страница 1: ......
Страница 27: ...A 26 MEMO...
Страница 29: ...MEMO...
Страница 101: ...3 34 Chapter 3 Specifications and Functions MEMO...
Страница 232: ...5 111 Chapter 5 Data Used for Positioning Control MEMO...
Страница 315: ...5 194 Chapter 5 Data Used for Positioning Control MEMO...
Страница 337: ...6 22 Chapter 6 Sequence Program Used for Positioning Control...
Страница 338: ...6 23 Chapter 6 Sequence Program Used for Positioning Control...
Страница 339: ...6 24 Chapter 6 Sequence Program Used for Positioning Control...
Страница 340: ...6 25 Chapter 6 Sequence Program Used for Positioning Control...
Страница 341: ...6 26 Chapter 6 Sequence Program Used for Positioning Control...
Страница 342: ...6 27 Chapter 6 Sequence Program Used for Positioning Control...
Страница 343: ...6 28 Chapter 6 Sequence Program Used for Positioning Control...
Страница 344: ...6 29 Chapter 6 Sequence Program Used for Positioning Control...
Страница 345: ...6 30 Chapter 6 Sequence Program Used for Positioning Control...
Страница 346: ...6 31 Chapter 6 Sequence Program Used for Positioning Control...
Страница 347: ...6 32 Chapter 6 Sequence Program Used for Positioning Control...
Страница 348: ...6 33 Chapter 6 Sequence Program Used for Positioning Control...
Страница 349: ...6 34 Chapter 6 Sequence Program Used for Positioning Control...
Страница 353: ...6 38 Chapter 6 Sequence Program Used for Positioning Control...
Страница 354: ...6 39 Chapter 6 Sequence Program Used for Positioning Control...
Страница 357: ...6 42 Chapter 6 Sequence Program Used for Positioning Control...
Страница 359: ...6 44 Chapter 6 Sequence Program Used for Positioning Control...
Страница 360: ...6 45 Chapter 6 Sequence Program Used for Positioning Control...
Страница 361: ...6 46 Chapter 6 Sequence Program Used for Positioning Control...
Страница 363: ...6 48 Chapter 6 Sequence Program Used for Positioning Control...
Страница 364: ...6 49 Chapter 6 Sequence Program Used for Positioning Control...
Страница 413: ...MEMO...
Страница 433: ...8 20 Chapter 8 OPR Control MEMO...
Страница 458: ...9 25 Chapter 9 Major Positioning Control MEMO...
Страница 593: ...10 30 Chapter 10 High Level Positioning Control MEMO...
Страница 625: ...11 32 Chapter 11 Manual Control MEMO...
Страница 659: ...12 34 Chapter 12 Expansion Control MEMO...
Страница 767: ...13 108 Chapter 13 Control Sub Functions MEMO...
Страница 813: ...14 46 Chapter 14 Common Functions MEMO...
Страница 831: ...15 18 Chapter 15 Dedicated Instructions MEMO...
Страница 846: ...16 15 Chapter 16 Troubleshooting MEMO...
Страница 892: ...16 61 Chapter 16 Troubleshooting MEMO...
Страница 971: ...Appendix 62 Appendices MEMO...
Страница 974: ......
Страница 975: ......