852
FX
3U
/FX
3UC
Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
37 Error Check Method and Error Code List
37.4 Error Code List and Action
Circuit error [M8066(D8066)]
0000
⎯
No error
6610
Stops
operation
LD, LDI is continuously used 9 times or more.
This error occurs when a combination of
instructions is incorrect in the entire circuit block or
when the relationship between a pair of instructions
is incorrect.
Modify the instructions in the program mode so that
their mutual relationship becomes correct.
6611
More ANB/ORB instructions than LD/LDI
instructions
6612
Less ANB/ORB instructions than LD/LDI
instructions
6613
MPS is continuously used 12 times or more.
6614
No MPS instruction
6615
No MPP instruction
6616
No coil between MPS, MRD and MPP, or incorrect
combination
6617
Instruction below is not connected to bus line:
STL, RET, MCR, P, I, DI, EI, FOR, NEXT, SRET,
IRET, FEND or END
6618
STL, MC or MCR can be used only in main
program, but it is used elsewhere (e.g. in interrupt
routine or subroutine).
6619
Invalid instruction is used in FOR-NEXT loop:
STL, RET, MC, MCR, I (interrupt pointer) or IRET.
6620
FOR-NEXT instruction nesting level exceeded
6621
Numbers of FOR and NEXT instructions do not
match.
6622
No NEXT instruction
6623
No MC instruction
6624
No MCR instruction
6625
STL instruction is continuously used 9 times or
more.
6626
Invalid instruction is programmed within STL-RET
loop:
MC, MCR, I (interrupt pointer), SRET or IRET.
6627
No RET instruction
6628
Invalid instruction is used in main program:
I (interrupt pointer), SRET or IRET
6629
No P or I (interrupt pointer)
6630
No SRET or IRET instruction
6631
SRET programmed in invalid location
6632
FEND programmed in invalid location
Operation error [M8067(D8067)]
0000
No error
6701
Continues
operation
•
No jump destination (pointer) for CJ or CALL
instruction
•
Label is undefined or out of P0 to P4095 due to
indexing
•
Label P63 is executed in CALL instruction;
cannot be used in CALL instruction as P63 is for
jumping to END instruction.
This error occurs in the execution of operation.
Review the program, or check the contents of the
operands used in the applied instructions.
Even if the syntax or circuit design is correct, an
operation error may still occur.
For example:
"T200Z" itself is not an error. But if Z had a value of
400, the timer T600 would be attempted to be
accessed. This would cause an operation error
since there is no T600 device available.
6702
CALL instruction nesting level is 6 or more
6703
Interrupt nesting level is 3 or more
6704
FOR-NEXT instruction nesting level is 6 or
more.
6705
Operand of applied instruction is inapplicable
device.
6706
Device number range or data value for operand of
applied instruction exceeds limit.
6707
File register is accessed without parameter setting
of file register.
Error codes in shaded columns are added in FX
3U
and FX
3UC
PLCs.
Error
code
PLC operation at
error occurrence
Contents of error
Action
Содержание FX3U Series
Страница 1: ...PROGRAMMING MANUAL Basic Applied Instructions Edition FX3U FX3UC SERIES PROGRAMMABLE CONTROLLERS ...
Страница 2: ......
Страница 889: ......