324
FX
3U
/FX
3UC
Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
13 High Speed Processing – FNC 50 to FNC 59
13.3 FNC 52 – MTR / Input Matrix
The figure below shows an example of the FX
3UC
-32MT-LT (sink input/sink output). For the wiring, refer to
the following manual of the used PLC.
→
FX
3U
Hardware Manual
Related device
Cautions
1. Number of occupied devices
1) Eight input points are occupied from the input device number specified in
.
2) "n" output points are occupied from the output device number specified in
.
When specifying the output in
, make sure that "n" output numbers specified in
does not
overlap the output specified in
.
2. Wiring
One diode of 0.1 A/50 V is required for each switch.
3. Output format
Use the transistor output format.
Device
Name
Description
M8029
Instruction execution complete
Turns ON after the first cycle operation.
Command
contact
M8029 (execution
complete)
[1]
[4]
1st column input is received.
+1
[2]
2nd column input is received.
20ms
D
1
D
1
[3]
[6]
[5]
COM1
+1
+2
+3
+4
+5
+6
+7
COM
+1
+2
+3
+4
+5
+6
+7
+1
D
2
D
2
+2
D
2
+3
D
2
+4
D
2
+5
D
2
+6
D
2
+7
D
2
S
S
S
S
S
S
S
S
D1
D1
D1
D1
D1
D1
D1
D1
Input (X) [sink]
Output (Y) [sink]
"n" points
are
occupied.
+10
D
2
D
2
D
2
D
2
D
2
D
2
D
2
+11
+12
+13
+14
+15
+16
D
2
+17
Diode
0.1A(50V)
2nd
column
1st
column
PLC
S
D
1
D
2
D
1
D
2
Содержание FX3U Series
Страница 1: ...PROGRAMMING MANUAL Basic Applied Instructions Edition FX3U FX3UC SERIES PROGRAMMABLE CONTROLLERS ...
Страница 2: ......
Страница 889: ......