864
FX
3U
/FX
3UC
Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
B Instruction Execution Time
B-2 Step Ladder Instruction Execution Time
*1.
M1536 to M3583, special M8256 to special M8511, S1024 to S4095
*2.
M1536 to M3583, special M8000 to special M8511
*3.
M3584 to M7679
Appendix B-2 Step Ladder Instruction Execution Time
Output instructions
OUT T D
0.71
0.71
T192 to T199, T246 to T511
11.6
µ
s in execution in ON status
8.2
µ
s in execution in OFF status
OUT C K
0.71
6.1
0.71
6.1
C235 to C255
9.5
µ
s in execution in ON status
9.0
µ
s in execution in OFF status
OUT C D
0.71
6.1
0.71
6.1
C235 to C255
9.5
µ
s in execution in ON status
9.0
µ
s in execution in OFF status
SET Y,M
0.065
0.129
µ
s in 2-step instruction
*2
0.193
µ
s in 3-step instruction
*3
SET S
4.7 or 6.6 + 0.9n
0.13
n: Number of recombination
4.7
µ
s when there is no
recombination
RST Y,M
0.065
0.129
µ
s in 2-step instruction
*2
0.193
µ
s in 3-step instruction
*3
RST S
4.6
0.13
RST T
0.45
0.45
RST C
0.45
5.8
0.45
4.8
RST D
5.4
⎯
0.195
⎯
PLS Y,M
0.257
0.321
µ
s in M3584 to M7679
PLF Y,M
0.257
0.321
µ
s in M3584 to M7679
Master control instructions
MC
4.3
4.7
MCR
3.9
⎯
Other instruction
NOP
0.065
End instruction
END
113.9 + 2.13X + 3.25Y
⎯
Even if FEND and END are used
together, execution time of only
END is required. X: Number of input
points, Y: Number of output points
Instruction
Execution time in ON status (
µ
s)
Execution time in OFF status (
µ
s)
Remarks
16-bit instruction
32-bit instruction
16-bit instruction
32-bit instruction
STL
5.1 + 1.6n
⎯
n: Number of recombination
n = 0: When there is no
recombination
RET
2.9
⎯
Instruction
Execution time in ON status (
µ
s)
Execution time in OFF status (
µ
s)
Remarks
16-bit instruction
32-bit instruction
16-bit instruction
32-bit instruction
Содержание FX3U Series
Страница 1: ...PROGRAMMING MANUAL Basic Applied Instructions Edition FX3U FX3UC SERIES PROGRAMMABLE CONTROLLERS ...
Страница 2: ......
Страница 889: ......