70
FX
3U
/FX
3UC
Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
4 Devices in Detail
4.1 Device Number List
4.
Devices in Detail
This chapter explains numeric values handled in the PLC as well as the roles and functions of various built-in
devices including I/O relays, auxiliary relays, state relays, counters and data registers.
These items are the basis for handling the PLC.
4.1
Device Number List
Device numbers are assigned as shown below.
For input relay numbers and output relay numbers when I/O extension equipment and special extension
equipment are connected to the PLC main unit, refer to the FX
3U
Hardware Edition.
Device name
Description
Reference
I/O relay
Input relay
X000 to X367
*1
248 points
Device numbers are octal.
The total number of inputs and outputs is
256.
Section 4.2
Output relay
Y000 to Y367
*1
248 points
Auxiliary relay
General type [variable]
M0 to M499
500 points
The setting can be changed between the
latched (battery backed) type and the non-
latched type using parameters.
Section 4.3
Latched (battery backed)
type [variable]
M500 to M1023
524 points
Latched (battery backed)
type [fixed]
M1024 to M7679
6656 points
Special type
*2
M8000 to M8511
512 points
Chapter 36
State relay
Initial state (general type
[variable])
S0 to S9
10 points
The setting can be changed between the
latched (battery backed) type and the non-
latched type using parameters.
Section 4.4
General type [variable]
S10 to S499
490 points
Latched (battery backed)
type [variable]
S500 to S899
400 points
Annunciator
(latched (battery backed)
type [variable])
S900 to S999
100 points
Latched (battery backed)
type [fixed]
S1000 to S4095
3096 points
Timer (on-delay timer)
100 ms
T0 to T191
192 points
0.1 to 3,276.7 sec
Section 4.5
100 ms [for subroutine or
interrupt routine]
T192 to T199
8 points
0.1 to 3,276.7 sec
10 ms
T200 to T245
46 points
0.01 to 327.67 sec
Retentive type for 1 ms
T246 to T249
4 points
0.001 to 32.767 sec
Retentive type for 100 ms T250 to T255
6 points
0.1 to 3,276.7 sec
1 ms
T256 to T511
256 points
0.001 to 32.767 sec