2.7 Types and Setting of Parameters
1
In
troduct
io
n
2
Ov
e
rv
ie
w
3
In
st
ru
ct
ion
Li
st
4
D
evi
ce
s
in
De
ta
il
5
Speci
fied t
h
e
D
evi
ce &
C
onst
a
nt
6
Bef
o
re
Pr
ogr
a
m
m
ing
7
Bas
ic
In
st
ru
cti
o
n
8
FNC0
0
-FNC0
9
P
ro
g
ra
m F
lo
w
9
FNC1
0
-FNC1
9
M
ov
e
&
C
om
par
e
10
FNC
20-
FNC
2
9
Ar
ith.
&
Logi
c
O
per
at
io
n
3. Click [Individual setting] button to display "Positioning instruction settings" dialog box.
In this dialog box, set the positioning table for each pulse output destination.
Set item
Contents of setting
Setting range
Y0
Set the positioning table for the pulse output destination Y000.
–
Y1
Set the positioning table for the pulse output destination Y001.
–
Y2
Set the positioning table for the pulse output destination Y002.
–
Y3
*1
Set the positioning table for the pulse output destination Y003.
–
Rotation direction signal
Set the output number of the rotation direction output signal.
Initial setting: Pulse output destination Y000: Y010
Pulse output destination Y001: Y011
Pulse output destination Y002: Y012
Pulse output destination Y003
*1
: Y013
→
Refer to the Positioning Control Manual.
Y000 to Y357
M0 to M7679
S0 to S4095
Head Address
Set the head number of devices storing the set data (pulse number and
frequency).
1600 devices are occupied starting from the head device number set
here without regard to the number of used axes.
Initial setting: R0
→
Refer to the Positioning Control Manual.
D0 to D6400
R0 to R31168
No.
This column shows the table number.
Numbers 1 to 100 can be set.
–
Positioning Instruction
Select the positioning type among the following:
DDVIT (Interrupt positioning instruction)
DPLSV (Variable speed output pulse instruction)
DDRVI (Relative positioning instruction)
DDRVA (Absolute positioning instruction)
→
Refer to the Positioning Control Manual.
–
Pulse
Set the pulse number output by the operation (instruction) set in
"Positioning Instruction" column.
→
Refer to the Positioning Control Manual.
Refer to the
Positioning Control
Manual.
Frequency [Hz]
Set the speed (pulse frequency) output by the operation (instruction) set
in "Positioning Instruction" column.
→
Refer to the Positioning Control Manual.
Refer to the
Positioning Control
Manual.
Up
This button transposes the selected line to the upper line.
–
Down
This button transposes the selected line to the lower line.
–
Insert
This button inserts a line in the currently selected position.
–
Delete
This button deletes the currently selected line.
–
Delete all lines
This button deletes the entire setting of the positioning table for the
selected pulse output destination.
–