730
FX
3U
/FX
3UC
Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
33 Extension File Register Control – FNC290 to FNC299
33.6 FNC295 – INITER / Initialize ER
33.6
FNC295 – INITER / Initialize ER
Outline
This instruction initializes (to “HFFFF” <K-1>) extension file registers (ER) in a memory cassette (flash
memory) before executing SAVER (FNC291) instruction.
Because INITER (FNC295) instruction is not supported in FX
3UC
PLCs former than Ver.1.30, use INITR
(FNC292) instruction instead.
→
For SAVER (FNC291) instruction, refer to Section 33.2.
→
For INITR (FNC292) instruction, refer to Section 33.3.
1. Instruction format
2. Set data
3. Applicable devices
Explanation of function and operation
1. 16-bit operation (INITER and INITERP)
“n” sectors of extension file registers in a memory cassette (flash memory) having the same device number
as
are initialized (to “HFFFF” <K-1>).
Initialization is executed in units of sector.
The table below shows the head device number in each sector:
Operand Type
Description
Data Type
Device number of extension register having a same device number of extension
file register to be initialized
It is possible to specify only the head device number in a sector of extension
registers.
16-bit binary
n
Number of sectors of extension registers and extension file registers to be
initialized
Oper-
and
Type
Bit Devices
Word Devices
Others
System User
Digit Specification
System User
Special
Unit
Index
Con-
stant
Real
Number
Charac-
ter String
Pointer
X Y M T C S D
.b KnX KnY KnM KnS
T
C
D
R U
\G
V
Z Modify K
H
E
"
"
P
3
3
n
3 3
Sector
number
Head device
number
Initialized device range
Sector
number
Head device
number
Initialized device range
Sector 0
R0
ER0 to ER2047
Sector 8
R16384
ER16384 to ER18431
Sector 1
R2048
ER2048 to ER4095
Sector 9
R18432
ER18432 to ER20479
Sector 2
R4096
ER4096 to ER6143
Sector 10
R20480
ER20480 to ER22527
Sector 3
R6144
ER6144 to ER8191
Sector 11
R22528
ER22528 to ER24575
Sector 4
R8192
ER8192 to ER10239
Sector 12
R24576
ER24576 to ER26623
Sector 5
R10240
ER10240 to ER12287
Sector 13
R26624
ER26624 to ER28671
Sector 6
R12288
ER12288 to ER14335
Sector 14
R28672
ER28672 to ER30719
Sector 7
R14336
ER14336 to ER16383
Sector 15
R30720
ER30720 to ER32767
P
FNC 295
INITER
Mnemonic
Operation Condition
16-bit Instruction
5 steps
INITR
Mnemonic
Operation Condition
Continuous
Operation
32-bit Instruction
⎯
⎯
INITRP
Pulse (Single)
Operation
S
S
S
FNC295
INITERP
n
S
Command