309
FX
3U
/FX
3UC
Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
12 Data Operation – FNC 40 to FNC 49
12.7 FNC 46 – ANS / Timed Annunciator Set
11
FN
C30-
FN
C39
R
o
ta
tion and
Sh
ift
12
FNC
4
0
-FNC49
D
a
ta
Op
e
ra
tio
n
13
FNC5
0
-FNC5
9
H
igh Speed
Pr
ocessi
ng
14
FM
C6
0
-F
NC6
9
H
and
y
In
st
ru
cti
o
n
15
FNC7
0
-FNC7
9
Ex
te
rn
a
l F
X
I
/O
D
evi
ce
16
FNC8
0
-FNC8
9
Ext
e
rnal
FX
D
evi
ce
17
F
N
C1
00
-F
NC
10
9
Da
ta
Tr
ansf
e
r 2
18
FN
C
110-FN
C
13
9
Fl
oat
ing P
o
in
t
19
FN
C
140-FN
C
149
Da
ta
O
per
at
io
n
2
20
FN
C
15
0-F
N
C
159
P
o
si
tioni
ng
C
ont
ro
l
Program example
1. Displaying a fault number using an annunciator
When the program for external fault diagnosis shown below is created and the contents of D8049 (smallest
state relay number in the ON status) are monitored, the smallest state relay number in the ON status among
S900 to S999 is displayed.
If two or more faults are present at the same time, the next smallest fault number is displayed after the fault of
the smallest fault number is cleared.
M8000
RUN monitor
Y005
Forward
movement
X000
FNC 46
ANS
Forward
end
X001
Upper
limit
X002
Lower
limit
FNC 46
ANS
X003
Continuous
X004
Cycle
FNC 46
ANS
M8049
Y005
X005
Forward
movement
M8048
Annunciator ON
Y006
Fault display
X007
Reset
FNC 47
ANRP
END
T 0
K 10
S900
T 1
K 20
S901
T 2
K100 S902
0
3
3
12
21
30
32
34
36
When M8049 turns ON, monitoring becomes valid.
If the forward end detection input X000 does not turn
ON within 1 second after the forward movement output
Y005 was driven, S900 turns ON.
If both the upper limit input X001 and the lower limit
input X002 are OFF for 2 seconds or more due to a dog
error, S901 turns ON.
The switch X004 is set to ON in one operation cycle of
the machine. If the switch X004 is not set to ON while
the continuous operation mode input X003 is ON in the
machine whose tact time is less than 10 seconds, S902
turns ON.
When either one among S900 to S999 turns ON, M8048
turns ON and the fault display output Y006 turns ON.
A state relay which was set to ON by the external fault
diagnosis program is set to OFF by the reset button
X007. Every time X007 is set to ON, an operation state
relay in the ON status with the smallest device number
is reset (set to OFF) in turn.
Содержание FX3U Series
Страница 1: ...PROGRAMMING MANUAL Basic Applied Instructions Edition FX3U FX3UC SERIES PROGRAMMABLE CONTROLLERS ...
Страница 2: ......
Страница 889: ......