4 Devices in Detail
4.3 Auxiliary Relay [M]
2. latched (battery backed) type
When the power is turned OFF while the PLC is operating, all of output relays and general type auxiliary
relays turn OFF.
When restoring the power again, all of output relays and general type auxiliary relays remain OFF except
those whose input condition is ON. In some output relays and auxiliary relays, however, the ON/OFF status
just before power failure should be stored and then replicated when restoring the power, depending on control
targets. In such a case, use latched (battery backed) type auxiliary relays.
Latch type devices are backed up by the battery built in the PLC.
→
For the details of backup method against power failure,
refer to Section 2.6.
The figure on the left shows an example of operations of
M600 (latched [battery backed] type device) in a self-
holding circuit.
When X000 turns ON and M600 turns ON in this circuit,
M600 holds its operation by itself even if X000 is
opened.
Because M600 is a latched (battery backed) type
device, it remains activated when the operation is
restarted even after X000 has turned OFF by power
failure. If an NC contact of X001 is opened when the
operation is restarted, however, M600 is deactivated.
The figure on the left shows a circuit by SET and RST
instructions.
1) Application example of latched (battery backed) type auxiliary relay
In some cases, the table should be restarted in the
same direction as the direction selected just before
power failure.
X000 = ON (at the left limit)
→
M600 = ON
→
The table
is driven rightward.
→
The power is turned OFF.
→
The
table is stopped in an intermediate position.
→
The table
is restarted (M600 = ON).
→
X001 = ON (at the right
limit)
→
M600 = OFF, M601 = ON
→
The table is driven
leftward.
2) Method for using a fixed latched (battery backed) type auxiliary relay as a general type auxiliary relay
When using a fixed latched (battery backed) type auxiliary relay as a general type auxiliary relay, provide
a reset circuit shown in the figure below around the head step in the program.
X000
M600
X001
PLC
Backup against power failure
(self-holding circuit)
M600
X000
X001
PLC
Backup against power failure
(set/reset circuit)
SET
M600
RST
M600
X000
M600
X001
M600
Rightward
drive
command
X001
M601
X000
M601
Leftward drive
command
Left limit
Limit switch
LS1 (X000)
Right limit
Limit switch
LS2 (X001)
Table in reciprocating motion
Motor with brake
M8002
Initial pulse
FNC 040
ZRST
M1024
M1999
M1024 to M1999 are initialized.