1. TROUBLESHOOTING FOR SERVO AMPLIFIER (DRIVE UNIT)
1 - 83
Alarm No.: 84
Name: Network module initialization error
Alarm content
The network module is not connected.
An error occurred at initialization of the network module.
Detail
No.
Detail name
Cause
Check method
Check result
Action
Target
84.1 Network
module
undetected
error
(1) The network module
was disconnected.
Check if the network
module is connected
correctly.
It is not connected
correctly.
Connect it correctly. [Other]
It is connected
correctly.
Check (2).
(2) Something near the
device caused it.
Check the noise,
ambient temperature,
etc. Refer to section
11.14 for the noise
reduction techniques.
It has a failure.
Take
countermeasures
against its cause.
It has no failure.
Check (3).
(3) The network module is
malfunctioning.
Replace the network
module, and then
check the
repeatability.
It is not repeatable.
Replace the network
module.
It is repeatable.
Check (4).
(4) The servo amplifier is
malfunctioning.
Replace the servo
amplifier, and then
check the
repeatability.
It is not repeatable.
Replace the servo
amplifier.