4 - 34
4. CONNECTION TO OMRON PLC
4.2 Serial Connection
4.2.21 Connecting to RS-422A
converter
Setting DIP switches
Set the DIP switches.
Switch
No.
Settings
Description
1
ON
Enable
Terminating
resistance
selection
2
OFF
4-wire
type
2-wire or 4-
wire selection
3
OFF
4-wire
type
2-wire or 4-
wire selection
5
ON
RS
control
enabled
RS control
selection for
RD
6
ON
RS
control
enabled
RS control
selection for
SD
DIP switch
O
N
1
2
3
4
5
6