4 - 18
4. CONNECTION TO OMRON PLC
4.2 Serial Connection
4.2.9
Connection Diagram
The following diagram shows the connection between the
GOT and the PLC.
RS-232 cable
(1) Connection diagram
RS232 connection diagram 1)
(For GT16, GT15, GT14, GT12, GT11, GT105 , GT104 )
*1
GT16: CD, GT15: CD, GT14:NC, GT12:NC, GT11: NC,
GT104 : NC, GT105 : NC
RS232 connection diagram 2)
(For GT16, GT15, GT14, GT12, GT11, GT105 , GT104 )
*1
GT16: CD, GT15: CD, GT14:NC, GT12:NC, GT11: NC,
GT104 : NC, GT105 : NC
RS232 connection diagram 3)
(For GT16, GT15, GT14, GT12, GT11, GT105 , GT104 )
*1
GT16: CD, GT15: CD, GT14:NC, GT12:NC, GT11: NC,
GT104 : NC, GT105 : NC
RS232 connection diagram 4)
(For GT1020, GT1030)
GOT side
1
2
3
4
5
6
7
8
9
OMRON PLC side
1
2
3
4
9
5
6
7
8
CD/NC
*1
RD(RXD)
SD(TXD)
ER(DTR)
SG
DR(DSR)
RS(RTS)
CS(CTS)
-
FG
SD
RD
RS
SG
CS
-
FR
ER
GOT side
1
2
3
4
5
6
7
8
9
OMRON PLC side
8
3
2
20
7
6
4
5
22
CD/NC
*1
RD(RXD)
SD(TXD)
ER(DTR)
SG
DR(DSR)
RS(RTS)
CS(CTS)
-
-
RD
SD
ER
SG
DR
RS
CS
-
GOT side
1
2
3
4
5
6
7
8
9
OMRON PLC side
1
2
3
4
7
5
6
8
20
CD/NC
*1
RD(RXD)
SD(TXD)
ER(DTR)
SG
DR(DSR)
RS(RTS)
CS(CTS)
-
FG
SD
RD
RS
SG
CS
-
-
ER
GOT side
(terminal block)
3
2
1
4
9
5
6
7
8
OMRON PLC side
SD
RD
ER
DR
SG
RS
CS
NC
NC
RD
SD
FG
RS
SG
CS
-
FR
ER
Содержание GOT 1000 Series
Страница 2: ......
Страница 76: ...1 46 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Страница 78: ......
Страница 114: ...2 36 2 CONNECTION TO IAI ROBOT CONTROLLER 2 7 Precautions ...
Страница 232: ...5 18 5 CONNECTION TO OMRON TEMPERATURE CONTROLLER 5 7 Precautions ...
Страница 254: ...6 22 6 CONNECTION TO KEYENCE PLC 6 4 Device Range that Can Be Set ...
Страница 404: ...14 14 14 CONNECTION TO PANASONIC SERVO AMPLIFIER 14 7 Precautions ...
Страница 426: ...15 22 15 CONNECTION TO PANASONIC INDUSTRIAL DEVICES SUNX PLC 15 6 Device Range that Can Be Set ...
Страница 432: ...REVISIONS 3 ...
Страница 435: ......