5 - 10
5. CONNECTION TO OMRON TEMPERATURE CONTROLLER
5.3 Connection Diagram
RS485 connection diagram 6)
*1
Pin No. of temperature controller differs depending on the model. Refer to the following.
*2
Terminating resistor should be provided for a temperature controller and an interface converter which will be terminating resistors.
*3
Set the terminating resistor of GOT side, which will be a terminal, to ”110
Ω
”.
1.4.3 Terminating resistors of GOT
GOT side
*3
SDA
SDB
RDA
RDB
SG
RSA
CSA
RSB
CSB
1
6
2
7
5
3
4
8
9
B(+)
A(-)
B(+)
A(-)
Temperature
controller side
*1
Temperature
controller side
*1
Temperature
controller side
*1
B(+)
A(-)
Terminating resistor(120 1/2W)
*2
Signal name
Model of temperature controller
E5AN
E5EN
E5CN
E5GN
E5ZN
Pin No.
Pin No.
Pin No.
A(-)
12
6
24
B(+)
11
5
23