Check first when you have a trouble
Protective functions
6 - 36
6.6.2
Motor or machine is making abnormal acoustic noise
Check
points
Possible cause
Countermeasure
Refer to
page
Input
signal
Disturbance due to EMI when frequency or
torque command is given from analog input
(terminal 1, 2, 4).
Take countermeasures against EMI.
Parameter
setting
Increase the Pr. 74 "Input filter time constant" if
steady operation cannot be performed due to
EMI.
Parameter
setting
No carrier frequency noises (metallic noises)
are generated.
In the initial setting, Pr. 240 "Soft-PWM
operation selection" is enabled to change
motor noise to an unoffending complex tone.
Therefore, no carrier frequency noises (metallic
noises) are generated.
Set Pr. 240 = "0" to disable this function.
The motor noise increases due to activation
of the carrier frequency automatic
reduction function when the motor is
driven overloaded.
Reduce the load.
Disable the automatic reduction function by
setting Pr. 260 "PWM frequency automatic
switchover" = "0".
Resonance occurs. (output frequency)
Set Pr. 31 to Pr. 36, Pr. 552 (Frequency jump).
When it is desired to avoid resonance
attributable to the natural frequency of a
mechanical system, these parameters allow
resonant frequencies to be jumped.
Resonance occurs. (carrier frequency)
Change Pr. 72 "PWM frequency selection"
setting.
Changing the PWM carrier frequency produces
an effect on avoiding the resonance frequency
of a mechanical system or a motor.
Auto tuning is not performed under
Advanced magnetic flux vector control.
Perform offline auto tuning.
Gain adjustment during PID control is
insufficient.
To stabilize the measured value, change the
proportional band (Pr. 129) to a larger value, the
integral time (Pr. 130) to a slightly longer time,
and the differential time (Pr. 134) to a slightly
shorter time.
Check the calibration of set point and measured
value.
The gain is too high under PM motor
control.
Check the setting values of Pr. 820 "Speed
control P gain 1" and Pr. 824 "Torque control P
gain 1 (current loop proportional gain)".
Others
Mechanical looseness
Adjust machine/equipment so that there is no
mechanical looseness.
⎯
Contact the motor manufacturer.
Motor
Operating with output phase loss
Check the motor wiring.
⎯
Содержание FR-F820-00046
Страница 2: ......
Страница 4: ......
Страница 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Страница 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Страница 874: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 900: ...Outline dimension drawings Specifications 8 26 ...
Страница 928: ...EC Declarations of Conformity Appendix A 28 A 6 EC Declarations of Conformity A 6 1 FR F820 FR F840 FR F842 series ...
Страница 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Страница 930: ...EC Declarations of Conformity Appendix A 30 ...
Страница 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Страница 932: ...EC Declarations of Conformity Appendix A 32 ...
Страница 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Страница 934: ...EC Declarations of Conformity Appendix A 34 ...
Страница 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Страница 936: ...EC Declarations of Conformity Appendix A 36 ...
Страница 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Страница 938: ...EC Declarations of Conformity Appendix A 38 ...
Страница 939: ......